FIR07-00695
| INSP-Sprinkler Rough-in | 9/11/2007 | 9/11/2007 | 9/11/2007 9:08:34 PM | P | CANC |
|
|
Inspection rescheduled.
|
FIR07-00285
| INSP-Sprinkler Rough-in | 9/10/2007 | 9/11/2007 | 9/11/2007 9:03:29 PM | P | FAIL |
|
|
See approved plans for areas in need of correction including overspacing at the data room, obstructed head at the second floor mech room, need to add one head in the riser room, blocked SW heads as noted, the antifreeze loop is not yet installed.
|
BLD07-00328
| FIRE-Final Inspection | 9/11/2007 | 9/11/2007 | 9/11/2007 8:59:02 PM | P | PART |
|
|
Corridor exiting (exit signs, EM lights, door hardware) is satisfactory. Permit final pending approved drawings reflecting actual floor plan, noted hardware at the existing safe doors to the room noted as "server" are not approved, need to final project related fire sprinkler permit prior to life safety final.
|
FIR07-00549
| INSP-Final Inspection | 9/11/2007 | 9/11/2007 | 9/11/2007 8:52:41 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR07-00441
| INSP-Alarm Testing | 9/11/2007 | 9/11/2007 | 9/11/2007 8:51:58 PM | A | PART |
|
|
Tested units at the fan deck, some items on this level are not yet amended for reinspection, the horn at the roof level sheet FA 2.4 does not function, notification devices at the underfloor area tested acceptable, EOL at the office area retested okay after corrections. Noted fire alarm for the office area is now approved.
|
FIR07-00549
| INSP-Alarm Testing | 9/10/2007 | 9/11/2007 | 9/11/2007 8:42:59 PM | A | PASS |
|
|
Fire alarm testing completed acceptable, noted missing cover at one junction box to be installed today per agreement.
|