ELE08-00701
| Final | 9/11/2008 | 9/11/2008 | 9/11/2008 4:44:54 PM | P | PASS |
|
|
equip field evaluated and labeled by ETL finak ok
|
ELE08-02511
| Permanent Service | 9/11/2008 | 9/11/2008 | 9/11/2008 4:43:41 PM | P | FAIL |
|
|
contr. called told him requirements for p/s, went to job site not ready and correction posted 110.26(F)(2) 250.52,104 (A)(1) grd or bond water system, 250.53(D)(1&2) and 250.56 shall provide 25ohms or less resistance or drive 2 grd rods
|
ELE08-01449
| Rough-In Permanent Service | 9/11/2008 | 9/11/2008 | 9/11/2008 3:13:30 PM | P | PASS |
|
|
Service Inspection Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe p/s u/g new ok
|
ELE08-01690
| Electrical Rough-In | 9/11/2008 | 9/11/2008 | 9/11/2008 1:54:21 PM | P | PART |
|
|
stopped at job site wsuc
|
ELE08-02503
| Electrical Rough-In | 9/11/2008 | 9/11/2008 | 9/11/2008 1:38:55 PM | P | PART |
|
|
The walls are ready for cover. Please look at the ceilings I know there are low voltage wires not tied up but let me know if any thing else needs fixed. Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig walls ok only needs to address low voltage in ceiling called
|
ELE08-01959
| Final | 9/11/2008 | 9/11/2008 | 9/11/2008 12:45:36 PM | P | PASS |
|
|
craig Phone #: ###-#### ok card signed
|
ELE08-02167
| Electrical Rough-In | 9/10/2008 | 9/11/2008 | 9/11/2008 10:17:13 AM | A | PART |
|
|
Contact is Jason. Please inspect underground electrical. Phone #: ###-#### Internet Inspection Request from: David Bonner u/g feeders ok
|
ESC08-00179
| General Inspection | 9/11/2008 | 9/11/2008 | 9/11/2008 10:16:36 AM | A | PART |
|
|
ok
|
ESC08-00627
| General Inspection | 9/11/2008 | 9/11/2008 | 9/11/2008 9:30:54 AM | A | PART |
|
|
site looks ok
|
ELE08-02500
| Temporary Service | 9/10/2008 | 9/11/2008 | 9/11/2008 9:30:03 AM | A | FAIL |
|
|
Bernd ###-#### corr posted talked with owner and ele contr, note ele contr did the wiring on homeowner permit, also GEC needs to rplaced or repair the damage, shall also terminate the GEC at the t/s not terminated to anything
|
ELE08-02500
| DOC - Permit Finaled | 9/11/2008 | 9/11/2008 | 9/11/2008 9:26:25 AM | A | PASS |
|
|
Bernd ###-####
|
ESC08-00193
| General Inspection | 9/11/2008 | 9/11/2008 | 9/11/2008 8:27:33 AM | A | PART |
|
|
site ok
|
ELE08-01805
| Electrical Rough-In | 9/10/2008 | 9/11/2008 | 9/11/2008 8:26:47 AM | A | PART |
|
|
Cover inspection for the grid. Please try to inspect this as early in the AM as possible. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean partial grid ok
|