FIR08-00239
| INSP-Sprinkler Rough-in | 9/10/2008 | 9/11/2008 | 9/15/2008 4:39:55 PM | A | PART |
|
|
See locations on approved plan set sheet FP5 for locations inspected to date on the 1st floor only, including areas north of the corridor main, noted issues in need of revision clouded and annotated.
|
FIR08-00597
| INSP-Sprinkler Rough-in | 9/11/2008 | 9/11/2008 | 9/11/2008 3:50:10 PM | P | PART |
|
|
Overhead installation at the grid ceiling is good for cover, atrium work is not finished.
|
BLD08-00379
| FIRE-Final Inspection | 9/11/2008 | 9/11/2008 | 9/11/2008 3:48:16 PM | P | CANC |
|
|
Incorrect permit number request.
|
FIR08-00610
| INSP-Final Inspection | 9/11/2008 | 9/11/2008 | 9/11/2008 2:38:04 PM | P | FAIL |
|
|
Sprinkler protection at the storage room exceeds 130 ft2, see approved plans for intended head layout. The remainder of work per this permit scope is okay for ceiling cover.
|
FIR08-00493
| INSP-Sprinkler Rough-in | 9/11/2008 | 9/11/2008 | 9/11/2008 2:34:30 PM | P | PART |
|
|
OH modifications are approved for cover at the drop ceilings per site inspection by T. Cobbley.
|
FIR08-00542
| INSP-Final Inspection | 9/10/2008 | 9/11/2008 | 9/11/2008 1:37:31 PM | A | FAIL |
|
|
Added heads below the ductwork need to match response type within the same fire area.
|
FIR08-00552
| INSP-Alarm Testing | 9/10/2008 | 9/11/2008 | 9/11/2008 1:35:51 PM | A | PASS |
|
|
Fire alarm work completed acceptable, field inspection passed, one relocated duct detector tested okay, a/v appliance heights AFF adjusted to comply with NFPA 72 req.
|
FIR08-00260
| INSP-Alarm Testing | 9/10/2008 | 9/11/2008 | 9/11/2008 1:32:07 PM | A | PASS |
|
|
Fire alarm system modifications tested satisfactory.
|
FIR07-00928
| INSP-Sprinkler Rough-in/Hydro | 9/11/2008 | 9/11/2008 | 9/11/2008 11:27:00 AM | A | PART |
|
|
Antifreeze system piping and drops at the 7th floor exterior balcony soffits above the patio areas only approved for cover with the exception of two heads to be relocated at the SW and NW corners due to spacing issues as discussed.
|
BLD08-00430
| FIRE-Final Inspection | 9/11/2008 | 9/11/2008 | 9/11/2008 10:41:11 AM | P | PASS |
|
|
Fire life safety finaled.
|
BLD08-00430
| FIRE-Alarm Testing | 9/10/2008 | 9/11/2008 | 9/11/2008 10:40:43 AM | A | DONE |
|
|
Project fire alarm testing has been completed.
|
BLD08-01452
| FIRE-Final Inspection | 9/10/2008 | 9/11/2008 | 9/11/2008 10:22:43 AM | A | PASS |
|
|
Scope of repair work completed acceptable, corrections provided, life safety inspection passed.
|
BLD08-00980
| FIRE-Final Inspection | 9/10/2008 | 9/11/2008 | 9/11/2008 9:38:25 AM | A | PASS |
|
|
Fire life safety passed field inspection, signature card was not available on site.
|