Inspections for the day of: Friday, September 11, 2009.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00333 FIR-Aging Inspection9/11/20099/11/20099/14/2009 4:55:31 PM NR
wip
BLD09-01136 FIRE-Conference9/11/20099/11/20099/11/2009 3:25:54 PMPDONE
I posted a "Do Not Occupy" sticker and spoke to the tenant about sign off's still required prior to occupancy. Mike Jordan was also notified of the situation.
BLD09-01209 FIRE-Sprinkler Rough-in9/11/20099/11/20099/11/2009 3:17:17 PMPPASS
Wrong inspection type called in.
BLD09-01209 FIRE-Final Inspection9/11/20099/11/20099/11/2009 3:16:23 PMPPASS
Life safety passed. Per Tim Woodard the racking permit has been received.
BLD09-00109 FIRE-Final Inspection9/11/20099/11/20099/11/2009 3:14:48 PMPFAIL
Both of the exit discharge lights need repaired and the emergency light in the north exit corridor from the new locker room needs repaired. I notified the general contractor that when the forward flush on the sprinkler system was performed all of the dirt and debri would be washed down to Hill Road and cause problems with Erosion Control.
FIR09-00317 INSP-Final Inspection9/11/20099/11/20099/11/2009 3:10:50 PMPPASS
See todays entry for corrections.
FIR09-00317 INSP-Final Inspection9/10/20099/11/20099/11/2009 3:10:09 PMAPASS
See todays entry for corrections.
FIR09-00317 INSP-Sprinkler Rough-in/Hydro9/9/20099/11/20099/11/2009 3:09:14 PMAPASS
The 24 hour air test passed on all three dry systems. The trip tests passed on dry system #2 and #3 but failed on system #1. Additional pendants are needed as discussed in the pockets separating the existing gym from the new locker rooms and the missing uprights on system #1 are needed. Per Scott system #1 does not need to be rehydro tested or 24 hour tested.
FIR09-00511 INSP-Final Inspection9/10/20099/11/20099/11/2009 12:37:10 PMAPASS
Permit finaled. The duct smoke detectors have been removed from the supply side of the hvac units by the mechanical contractor and the duct smoke detectors have been removed off of the hvac unit located in northeast corner of the building. This unit was rated at 1850cfm per the mechanical contractor.
BLD09-01465 FIRE-Final Inspection9/8/20099/11/20099/11/2009 12:32:57 PMAPASS
Life safety passed. I made two trips for this inspection to give the owner time to correct issues.
FIR08-00382 INSP-Sprinkler Rough-in/Hydro9/10/20099/11/20099/11/2009 9:58:23 AMAPASS
The fire alarm is passed in the first floor shower room and isolation room.
BLD07-01846 FIRE-Final Inspection9/10/20099/11/20099/11/2009 9:57:46 AMAPART
The life safety is passed in the first floor shower room and isolation room.
BLD09-01552 FIRE-Final Inspection9/10/20099/11/20099/11/2009 8:53:44 AMAFAIL
Travis Bailey ###-#### I left a message on the contacts voice mail and went to the tenant space but did not gain access.