Inspections for the day of: Friday, September 11, 2015.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-02845 Electrical Rough-In9/11/20159/11/20159/11/2015 2:42:13 PMPPASS
Phone #: ###-#### Kitchen west wall only rough in ok cover
ELE15-01812 Electrical Rough-In9/10/20159/11/20159/11/2015 1:41:23 PMPPASS
Underground Inspection Phone #: ###-#### Inspection requested via web by William Salts Carwash interior unergound complete. Rough in ok cover
ELE15-02243 Final9/10/20159/11/20159/11/2015 1:00:59 PMPPASS
Phone #: ###-#### Inspection requested via web by Celinda Winters Final ok
ELE15-02684 Rough-In Permanent Service9/11/20159/11/20159/11/2015 12:21:03 PMPPASS
Gary is the onsite contact at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough in ok cover p/s u/g n ok
ELE13-00996 ELE-Aging Inspection9/11/20159/11/20159/11/2015 11:30:36 AM DONE
Still under construction
ELE13-00997 ELE-Aging Inspection9/11/20159/11/20159/11/2015 11:30:10 AM DONE
Still under construction
ELE13-00998 ELE-Aging Inspection9/11/20159/11/20159/11/2015 11:29:19 AM DONE
Still under construction
ELE10-01593 ELE-Aging Inspection9/11/20159/11/20159/11/2015 10:56:39 AM DONE
Owner refusing to comply. Turning over to City Attorney
ELE15-02035 Permanent Service9/10/20159/11/20159/11/2015 10:50:38 AMAPASS
Roger Phone #: ###-#### p/s u/g n ok
ELE15-02035 Electrical Rough-In9/11/20159/11/20159/11/2015 10:34:09 AMPFAIL
Roger Phone #: ###-#### 110.14- Terminals for conductors shall be identified for finely stranded wire. Stranded wire connections shall have connectors that involve all strands of a conductor to be involved in connection.
ELE15-02429 Final9/10/20159/11/20159/11/2015 10:21:53 AMACANC
Pool light potting compound, Equipotential plane, pool equipment Phone #: ###-#### Inspection requested via web by Lars Johnson Needed rough in inspection
ELE15-02429 Electrical Rough-In9/11/20159/11/20159/11/2015 9:51:45 AMPPASS
Pool light potting compound, Equipotential plane, pool equipment Phone #: ###-#### Inspection requested via web by Lars Johnson Potting, perimenter bond, rails, ladder, rough in ok cover
ELE15-02404 Final9/10/20159/11/20159/11/2015 9:32:55 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn (A) Dwelling Units. All 120-volt, single-phase, 15- and
20-ampere branch circuits supplying outlets or devices installed in dwelling unit bedroom shall be AFCI protected. Spare bed and smokes.
ELE15-02598 Electrical Rough-In9/10/20159/11/20159/11/2015 8:40:04 AMAPASS
Ceiling inspect for storage area at customer service. Contact is Jay Sprik. Phone #: ###-#### Inspection requested via web by Richard Montgomery Storage rm grid rough in ok cover
ELE15-01111 Electrical Rough-In9/11/20159/11/20159/11/2015 8:18:56 AMPFAIL
NEC 210.62- Show Windows. At least one 125-volt, singlephase, 15- or 20-ampere-rated receptacle outlet shall be installed within 450 mm (18 in.) of the top of a show window for each 3.7 linear m (12 linear ft) or major fraction thereof of show window area measured horizontally at its maximum width.