Inspections for the day of: Tuesday, September 11, 2018.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-03970 Final9/10/20189/11/20189/11/2018 4:05:15 PMPNR
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- Not ready refrigeration crew still has some work to finish
MEC18-03574 Pressure Test9/11/20189/11/20189/11/2018 3:53:15 PMPPASS
Contact: Robert Church ###-####. Phone #: ###-#### Inspection requested via web by Brent Lacy- 20lb gas pressure test to two new RTU's ok- piping R/I ok
MEC18-03960 Final9/4/20189/11/20189/11/2018 3:52:03 PMPPASS
Please call Zoe Brunelle prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- A/C fuse sizes ok- furnace ac coil co ok
MEC18-04393 Pressure Test9/11/20189/11/20189/11/2018 3:13:23 PMPFAIL
David Phone #: ###-####
- 20lb gas pressure test fail gauge would not zero
MEC18-03811 Rough-in9/11/20189/11/20189/11/2018 2:56:04 PMPFAIL
105,106,205,206,305,306 Phone #: ###-#### Inspection requested via web by Gary Reeves
-105 nail plate- floor boot needs sealed- supply trunk at furnace needs sealer
106- nail plate- fresh air duct needs sealer
205- nail plate- dryer box needs sealer on the back side
206- line set insulation has a rip- dryer box needs sealed
306- duct seal supply trunk at furnace and fresh air duct needs sealed at furnace
MEC18-01867 Final9/6/20189/11/20189/11/2018 2:11:24 PMPFAIL
Please call Gary 30 min prior to arrival Phone #: ###-#### Inspection requested via web by Andrea Grigsby- condensate needs supported out by the A/C and needs a 90 elbow turned down
MEC18-04080 Final9/10/20189/11/20189/11/2018 1:50:08 PMPPASS
field super: chad robertson Phone #: ###-#### Inspection requested via web by Lisa Whitney
- furnace relocate coil co ok
MEC18-04348 Final9/5/20189/11/20189/11/2018 1:28:55 PMPFAIL
Phone #: ###-#### Inspection requested via web by Marisa Hone- condensate needs to be piped out of the foundation and turned down with a 90 elbow
MEC18-02192 Rough-in9/10/20189/11/20189/11/2018 10:29:27 AMAPART
Request above ceiling Bld C and Connect area duct seal inspection C ; D.
Please contact Rob ###-#### with any questions or concerns.
Phone #: ###-#### Inspection requested via web by Heather Gransbery
- duct seal for connect area from D to C on NW side ok- bldC common area insulation ok up to gridline 3.4 cover ok -bldC south and west corridors insulation ok
MEC18-04169 Rough-in9/10/20189/11/20189/11/2018 10:11:25 AMAPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok
MEC18-04169 Pressure Test9/10/20189/11/20189/11/2018 10:11:08 AMAPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pressure test ok-2x 5lb flue pressure test ok
MEC18-04045 Rough-in9/10/20189/11/20189/11/2018 8:55:43 AMAFAIL
Phone #: ###-#### Inspection requested via web by Ashley Stegemann- indoor firplace R/I ok- outdoor fireplace fail- combustrible material needs to be removed on the face of the fireplace (sheeting on the top and sides)
MEC12-02306 Mec-Aging Inspection9/11/20189/11/20189/11/2018 8:36:47 AM DONE
called contractor and left a message.
MEC17-04330 Final9/10/20189/11/20189/11/2018 8:32:45 AMAPASS
Please call tech if you need access/have questions: ###-#### Phone #: ###-#### Inspection requested via web by Melissa Skinner- RTU fuses ok- plumbing vents 10' away from fresh air intake- gas line supported- final ok