FIR18-00356
| INSP-Sprinkler Rough-in | 9/10/2018 | 9/11/2018 | 9/11/2018 12:00:00 AM | A | PASS |
|
|
Forrest inspection comments- Remainder of overhead fire sprinkler work at phase two 1st floor approved for ceiling cover. Refer to dated annotations on stamped plan sheet. Contractor to provide matched temp. heads
in common spaces between the new remodel area (200 deg. QR) and existing area (155 deg. QR) as discussed.
roy nelson Phone #: ###-#### >> Inspection requested via web by Brodie Stenquist
|
FIR18-00478
| INSP-Final Inspection | 9/10/2018 | 9/11/2018 | 9/11/2018 12:00:00 AM | A | PASS |
|
|
Forrest inspection comments-Final inspection for the scope of fire sprinkler work completed satisfactory. Permit final approved, signature card not available on site. Give Brian a call prior to heading out there. Phone #: ###-#### >> Inspection requested via web by Sam Ball
|
NAF18-00104
| INSP-Final | 9/10/2018 | 9/11/2018 | 9/11/2018 12:00:00 AM | P | FAIL |
|
|
1- door hardware shall have thumb turn removed. Or revise plans as only one exit is required from this space. As exit sigh in installed the doors shall be fully compliant.
2- provide signage over exit doors, This door to remain unlocked when building is occupied.
Call for reinspection. Call prior to going Phone #: 2088697423 >> Inspection requested via mobile web by Dillon
|
FIR18-00493
| INSP-Final Inspection | 9/11/2018 | 9/11/2018 | 9/11/2018 12:00:00 AM | P | PASS |
|
|
Forrest inspection comments-Scope of permit work passed final inspection. Occupancy request card signed and dated for fire sprinkler work. Terry Phone #: ###-####
|
FIR18-00489
| INSP-Sprinkler Rough-in/Hydro | 9/10/2018 | 9/11/2018 | 9/11/2018 12:00:00 AM | P | PASS |
|
|
Forrest inspection comments-Overhead rough-in inspection completed and passed. Freeze protection/insulation is not yet provided, approval for ceiling installation pending an additional for cover inspection. OH hydrostatic
test also completed and passed. Underground supply line is not yet installed.
Call Anthony before heading out, thank you! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
|