Inspections for the day of: Thursday, September 12, 2002.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-02622 Final9/11/20029/12/20029/12/2002 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 09/11/2002 at 11:38:53. Contact: ###-####.
ELE02-02639 Electrical Rough-In9/11/20029/12/20029/12/2002 12:00:00 AMAPART
###-#### u/g ok 9/12/2002 1:57:49 PM
ELE02-02432 Final9/11/20029/12/20029/12/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 09/11/2002 at 13:46:16. Contact: ###-####. ok card signed 9/12/2002 12:03:14 PM
ELE02-02836 Rough-In Permanent Service9/11/20029/12/20029/12/2002 12:00:00 AMAFAIL
###-#### cor. posterd called 240.24(E) remove panel that is in bathroom, 210.52(A)(B) outlet in dinnnr shall be on small appliance branch circuit, note need too encase rebar in concrete where exposed to earth 9/12/2002 11:43:55 AM
ELE02-02841 Rough-In Permanent Service9/12/20029/12/20029/12/2002 12:00:00 AMPFAIL
###-#### cor. posted called 300.4 nail plates and 11/4 inches, 314.43, 314.16 box fill upstairs bath outlet 334.28 bending cable less tan 5 times the diameter 9/12/2002 2:57:14 PM
ELE02-02842 Rough-In Permanent Service9/12/20029/12/20029/12/2002 12:00:00 AMPPASS
rowdy ###-#### r/i ok called Rowdy needs #12 pigtail for disposal switch and outside back outlet box replaced no nails allowed in box


p/s u/g new ok 9/12/2002 3:19:13 PM
ELE02-02622 Final9/12/20029/12/20029/12/2002 12:00:00 AMPPASS
ok 9/12/2002 5:12:26 PM
ELE02-01692 Permanent Service9/12/20029/12/20029/12/2002 12:00:00 AMPPASS
terry ###-####

p/s o/h rec. ok 9/12/2002 4:08:12 PM
ELE02-02772 Electrical Rough-In9/12/20029/12/20029/12/2002 12:00:00 AMPPART
harold ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie walls ok 9/12/2002 6:11:57 PM
ELE02-02773 Electrical Rough-In9/12/20029/12/20029/12/2002 12:00:00 AMPPART
harold ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie walls ok 9/12/2002 6:12:08 PM
ELE02-02774 Electrical Rough-In9/12/20029/12/20029/12/2002 12:00:00 AMPPART
harold ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie walls ok 9/12/2002 6:12:19 PM