Inspections for the day of: Tuesday, September 12, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02332 Final9/12/20069/12/20069/12/2006 4:30:19 PMPFAIL
spencer; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie--call 1st for access called, left corr notice, nec 410.4(D) up bath fixture shall be listed as suitable for damp location by shaower, 314.21 boxes with flush type covers shall have drywall repaired so no gap over 1/8" at edge of box (out front and microwave), 406.5, 404.9 faceplates shall seat against mounting surface,BCC all make-up shall be done - disposal installed tile in bath for recpt?
ELE06-02550 Final9/12/20069/12/20069/12/2006 3:49:45 PMPFAIL
spencer; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie--call 1st for access called, left corr notice, nec 250.53(G) electrode shall be flush with or below ground ,406.5&404.9 faceplates shall seat against mounting surface, 406.4 recpts shall be securely fastened in place, 404.4 switch shall not be installed in tub space, BCC tile work shall be done in bath
ELE06-02024 Final9/12/20069/12/20069/12/2006 3:26:29 PMPFAIL
spencer; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie--call 1st for access called, left corr notice, nec 406.4(D) recpt faces shall be flush with or project from faceplates(all), 406.4 recpts shall be securely fastened in place(garage), 406.5&404.9 faceplates shall seat against mounting surface,BCC all make-up shall be done(ac)
ELE06-01778 Final9/12/20069/12/20069/12/2006 2:56:50 PMAFAIL
solar post light Internet Inspection Request from: Melyne Davis called, left message, left corr notice, nec 406.5 & 404.9 faceplates shall seat against mounting surface,406.4 recpt faces shall be flush with or project from faceplates,Bcc all make-up shall be done-mbr lites shall operate, 3-way switch up hall shall operate, garage gfci to left of panel shall operate
ELE06-01866 Final9/11/20069/12/20069/12/2006 2:20:44 PMPPASS
calvin; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
ELE06-03301 Rough-In Permanent Service9/12/20069/12/20069/12/2006 1:44:56 PMPPASS
darrin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok, p/s u/g n ok
ELE06-01438 Permanent Service9/11/20069/12/20069/12/2006 11:04:11 AMAFAIL
daniel - call prior to insp for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left corr notice, nec 250.24(A)(1) gec shall be connected to terminal or bus to which the grounded service conductor is connected at the service, 310.4 paralled conductors shall be electrically joined at both ends, 110.12(A) unused openings shall be closed, 312.5 abrasion protection shall be provided for all conductors entering enclosure,250.53(G) rods shall be flush with surface, BCC all make-up shall be done, taping for phases done, Note: no access to inside, could determine more corrections
ELE06-02887 Rough-In Permanent Service9/11/20069/12/20069/12/2006 10:48:46 AMAPART
Site underground inspection.; Phone #: ###-#### Internet Inspection Request from: Tina Payne north 1/2 u/g for site liting ok to cover
ELE06-03241 Final9/11/20069/12/20069/12/2006 10:23:30 AMAPASS
Butch, call 1st b4 going out; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
ELE06-02741 Final9/11/20069/12/20069/12/2006 10:13:55 AMAPASS
Scheduled by a contractor via Hello! on 9/11/2006 at 6:36:27 PM. Contact: ###-####. ok to final
ELE06-03390 Final9/11/20069/12/20069/12/2006 10:00:00 AMAPASS
Jason; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz ok to final
ELE06-02464 Final9/12/20069/12/20069/12/2006 9:22:06 AMAPART
Phone #: ###-#### Internet Inspection Request from: Jim Williams ok to final
ELE06-03178 Electrical Rough-In9/11/20069/12/20069/12/2006 9:02:18 AMAPASS
ANY QUESTIONS PLEASE CALL JESSIE COLLINGSWORTH; Phone #: ###-#### Internet Inspection Request from: Jeff Radford walls only ok to cover
ELE06-00113 Electrical Rough-In9/11/20069/12/20069/12/2006 8:48:41 AMAPART
This is for a ceiling rough-in inspection. Contact Greg Pack ; Phone #: ###-#### Internet Inspection Request from: Shelli Daylong ok to cover anop