Inspections for the day of: Friday, September 12, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-01745 FIRE-Final Inspection9/12/20089/12/20089/12/2008 4:25:31 PMPFAIL
Provide exit discharge lighting as required on the approved plans, mount the fire extinguishers and provide a quick test of the notification circuit to verify that the audio/visuals that were temporarily removed still function correctly.
BLD08-01127 FIRE-Final Inspection9/12/20089/12/20089/12/2008 4:14:04 PMPFAIL
This inspection actually turned into a conference on the remodeled area of the existing building next to the break room. I agreed that people could move in when a emergency light/exit sign is installed over the exit way to the corridor.
FIR08-00526 INSP-Sprinkler Rough-in/Hydro9/12/20089/12/20089/12/2008 4:11:01 PMPPART
See the city approved plans for the piping for the three pendants in the bakery that are ok to cover.
FIR08-00410 INSP-Supply line flush9/11/20089/12/20089/12/2008 2:52:02 PMPPASS
The underground flush passed
FIR08-00203 INSP-Final Inspection9/10/20089/12/20089/12/2008 1:20:50 PMACANC
Phone #: ###-#### Internet Inspection Request from: bruce stricker
BLD08-01396 FIRE-Final Inspection9/12/20089/12/20089/12/2008 1:20:12 PMPFAIL
Repair the inoperative light in the southwest emergency light and remove the thumb turn dead bolts from both east and west doors at the northwest corner.
FIR07-01032 FIR-Aging Inspection9/12/20089/12/20089/12/2008 11:15:04 AM NR
Work is in progress
FIR07-00605 INSP-Final Inspection9/11/20089/12/20089/12/2008 11:00:50 AMAFAIL
This inspection only covered the first floor today. See the city approved plans for locations of deficiencies which include old fire alarm devices that have not been removed, dampers that due not operate and a strobe that is mounted too low. Also the fire alarm plans need to be resubmitted showing the access controled egress doors on the east and north sides of the building that are not connected to the fire alarm system as required by IFC chapter 10