BLD08-01745
| FIRE-Final Inspection | 9/12/2008 | 9/12/2008 | 9/12/2008 4:25:31 PM | P | FAIL |
|
|
Provide exit discharge lighting as required on the approved plans, mount the fire extinguishers and provide a quick test of the notification circuit to verify that the audio/visuals that were temporarily removed still function correctly.
|
BLD08-01127
| FIRE-Final Inspection | 9/12/2008 | 9/12/2008 | 9/12/2008 4:14:04 PM | P | FAIL |
|
|
This inspection actually turned into a conference on the remodeled area of the existing building next to the break room. I agreed that people could move in when a emergency light/exit sign is installed over the exit way to the corridor.
|
FIR08-00526
| INSP-Sprinkler Rough-in/Hydro | 9/12/2008 | 9/12/2008 | 9/12/2008 4:11:01 PM | P | PART |
|
|
See the city approved plans for the piping for the three pendants in the bakery that are ok to cover.
|
FIR08-00410
| INSP-Supply line flush | 9/11/2008 | 9/12/2008 | 9/12/2008 2:52:02 PM | P | PASS |
|
|
The underground flush passed
|
FIR08-00203
| INSP-Final Inspection | 9/10/2008 | 9/12/2008 | 9/12/2008 1:20:50 PM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: bruce stricker
|
BLD08-01396
| FIRE-Final Inspection | 9/12/2008 | 9/12/2008 | 9/12/2008 1:20:12 PM | P | FAIL |
|
|
Repair the inoperative light in the southwest emergency light and remove the thumb turn dead bolts from both east and west doors at the northwest corner.
|
FIR07-01032
| FIR-Aging Inspection | 9/12/2008 | 9/12/2008 | 9/12/2008 11:15:04 AM | | NR |
|
|
Work is in progress
|
FIR07-00605
| INSP-Final Inspection | 9/11/2008 | 9/12/2008 | 9/12/2008 11:00:50 AM | A | FAIL |
|
|
This inspection only covered the first floor today. See the city approved plans for locations of deficiencies which include old fire alarm devices that have not been removed, dampers that due not operate and a strobe that is mounted too low. Also the fire alarm plans need to be resubmitted showing the access controled egress doors on the east and north sides of the building that are not connected to the fire alarm system as required by IFC chapter 10
|