Inspections for the day of: Monday, September 12, 2011.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00143 FIR-Aging Inspection9/12/20119/12/20119/15/2011 1:47:58 PM NR
I splok with Ernie, mall managment, and Joe with Lightining Electric, about getting this project inspected and finaled.
BLD07-02498 FIRE-Conference9/9/20119/12/20119/14/2011 3:50:15 PMADONE
Follow up for racking.
FIR11-00423 INSP-Sprinkler Rough-in9/12/20119/12/20119/12/2011 3:57:55 PMPCANC
overbooked
BLD11-01981 FIRE-Final Inspection9/12/20119/12/20119/12/2011 3:56:31 PMPCANC
overbooked
BLD11-00862 FIRE-Final Inspection9/12/20119/12/20119/12/2011 3:53:29 PMPFAIL
Mount fire extinguishers, provide exit sign and panic hardware at the doors to the "card" room and remove the brackets from the exit doors.
FIR11-00242 INSP-Sprinkler Rough-in/Hydro9/12/20119/12/20119/12/2011 3:52:42 PMPPART
Piping in the office area can be covered except in all of the areas marked in red as discussed due to missing seismic bracing.
BLD10-02666 FIRE-Conference9/12/20119/12/20119/12/2011 3:51:52 PMPDONE
Discussed covering of the insulation with Todd
FIR11-00464 INSP-Sprinkler Rough-in/Hydro9/12/20119/12/20119/12/2011 3:51:26 PMPPASS
The underground cover passed.
FIR11-00330 INSP-Final Inspection9/12/20119/12/20119/12/2011 3:50:26 PMPCANC
To be canceled per Jeff
BLD11-00781 FIRE-Final Inspection9/9/20119/12/20119/12/2011 12:08:13 PMPCANC
Cancel per Chris Palmer
FIR11-00474 INSP-Sprinkler Rough-in9/12/20119/12/20119/12/2011 11:56:40 AMPFAIL
Todays inspection was for the gridded area which failed due to the actual pendant head layout not matching the approved plans. This same area happens to be a remote area. Plans need to be resubmitted showing the actual layout and any hydraulic remote area modifications if needed.
BLD11-02077 FIRE-Final Inspection9/8/20119/12/20119/12/2011 10:43:45 AMAFAIL
See the city approved plans for corrections listed in red which include door hardware, electrical outlets and fire extinguishers.
BLD11-02035 FIRE-Final Inspection9/9/20119/12/20119/12/2011 9:37:22 AMAFAIL
A permit for the relocation of the horn is required. This work has already been done and will need to be double fee'd. Also the door hardware to the new closet needs to be single action approved type.
BLD11-01826 FIRE-Final Inspection9/9/20119/12/20119/12/2011 8:53:46 AMAFAIL
Need the project related fire sprinkler permit to be issued, work performed and inspection passed. Life safety will be ok to pass when that is done.