FIR08-00143
| FIR-Aging Inspection | 9/12/2011 | 9/12/2011 | 9/15/2011 1:47:58 PM | | NR |
|
|
I splok with Ernie, mall managment, and Joe with Lightining Electric, about getting this project inspected and finaled.
|
BLD07-02498
| FIRE-Conference | 9/9/2011 | 9/12/2011 | 9/14/2011 3:50:15 PM | A | DONE |
|
|
Follow up for racking.
|
FIR11-00423
| INSP-Sprinkler Rough-in | 9/12/2011 | 9/12/2011 | 9/12/2011 3:57:55 PM | P | CANC |
|
|
overbooked
|
BLD11-01981
| FIRE-Final Inspection | 9/12/2011 | 9/12/2011 | 9/12/2011 3:56:31 PM | P | CANC |
|
|
overbooked
|
BLD11-00862
| FIRE-Final Inspection | 9/12/2011 | 9/12/2011 | 9/12/2011 3:53:29 PM | P | FAIL |
|
|
Mount fire extinguishers, provide exit sign and panic hardware at the doors to the "card" room and remove the brackets from the exit doors.
|
FIR11-00242
| INSP-Sprinkler Rough-in/Hydro | 9/12/2011 | 9/12/2011 | 9/12/2011 3:52:42 PM | P | PART |
|
|
Piping in the office area can be covered except in all of the areas marked in red as discussed due to missing seismic bracing.
|
BLD10-02666
| FIRE-Conference | 9/12/2011 | 9/12/2011 | 9/12/2011 3:51:52 PM | P | DONE |
|
|
Discussed covering of the insulation with Todd
|
FIR11-00464
| INSP-Sprinkler Rough-in/Hydro | 9/12/2011 | 9/12/2011 | 9/12/2011 3:51:26 PM | P | PASS |
|
|
The underground cover passed.
|
FIR11-00330
| INSP-Final Inspection | 9/12/2011 | 9/12/2011 | 9/12/2011 3:50:26 PM | P | CANC |
|
|
To be canceled per Jeff
|
BLD11-00781
| FIRE-Final Inspection | 9/9/2011 | 9/12/2011 | 9/12/2011 12:08:13 PM | P | CANC |
|
|
Cancel per Chris Palmer
|
FIR11-00474
| INSP-Sprinkler Rough-in | 9/12/2011 | 9/12/2011 | 9/12/2011 11:56:40 AM | P | FAIL |
|
|
Todays inspection was for the gridded area which failed due to the actual pendant head layout not matching the approved plans. This same area happens to be a remote area. Plans need to be resubmitted showing the actual layout and any hydraulic remote area modifications if needed.
|
BLD11-02077
| FIRE-Final Inspection | 9/8/2011 | 9/12/2011 | 9/12/2011 10:43:45 AM | A | FAIL |
|
|
See the city approved plans for corrections listed in red which include door hardware, electrical outlets and fire extinguishers.
|
BLD11-02035
| FIRE-Final Inspection | 9/9/2011 | 9/12/2011 | 9/12/2011 9:37:22 AM | A | FAIL |
|
|
A permit for the relocation of the horn is required. This work has already been done and will need to be double fee'd. Also the door hardware to the new closet needs to be single action approved type.
|
BLD11-01826
| FIRE-Final Inspection | 9/9/2011 | 9/12/2011 | 9/12/2011 8:53:46 AM | A | FAIL |
|
|
Need the project related fire sprinkler permit to be issued, work performed and inspection passed. Life safety will be ok to pass when that is done.
|