Inspections for the day of: Thursday, September 12, 2013.
Number of inspections: 14
Percentage of inspections complete: 86 %
Percentage of inspections not complete: 14 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00350 INSP-Supply line flush9/5/20139/6/2013 P 
Nate is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
FIR13-00348 INSP-Supply line flush9/5/20139/6/2013 P 
Nate is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
FIR13-00487 INSP-Final Inspection9/11/20139/12/20139/12/2013 5:30:43 PMPPART
Final pending points map at the panel, zones 5 and 6 are reversed, need record of completion paperwork. Plugs at duct detector removed while on site. Remainder of inspection items passed including MP station, SD, kitchen hood, flow and tamper, DD, panel batteries, panel items.
FIR13-00230 INSP-Sprinkler Rough-in/Hydro9/11/20139/12/20139/12/2013 5:22:56 PMPFAIL
Time limitations per NFPA 13 for dry system water delivery were exceeded for the 1st floor system.
FIR13-00446 INSP-Final Inspection9/11/20139/12/20139/12/2013 5:18:54 PMPFAIL
Need to adjust distance from the nozzles to the cooking appliances per mfg. data sheets.
FIR13-00482 INSP-Sprinkler Rough-in9/11/20139/12/20139/12/2013 5:16:50 PMPPART
Inspection for work completed to date okayed.
FIR13-00463 INSP-Final Inspection9/11/20139/12/20139/12/2013 5:12:11 PMPPASS
Hood suppression system operated correctly under test conditions. Permit finaled.
FIR13-00230 INSP-Sprinkler Rough-in/Hydro9/11/20139/12/20139/12/2013 12:02:26 PMAPART
Completed hydrostatic testing of the new dry system piping at the 4th, 5th floors, and riser.
FIR12-00090 FIR-Aging Inspection9/12/20139/12/20139/12/2013 11:02:29 AM PEND
FIR12-00302 FIR-Aging Inspection9/12/20139/12/20139/12/2013 11:01:26 AM PEND
FIR12-00299 FIR-Aging Inspection9/12/20139/12/20139/12/2013 11:00:06 AM PEND
FIR13-00266 INSP-Sprinkler Rough-in9/11/20139/12/20139/12/2013 10:46:27 AMAPART
Items on the previous correction notice are not yet finished at some locations including ssu's at the ramp, missing seismic brace, missing section of galv pipe, trapped outlet. Verified missing coverage has been added, hangers adjusted, head cages on, adjustments, etc. are finished. New valve and trim monitoring not yet finished. Discussed trip test schedule.
FIR13-00434 INSP-Sprinkler Rough-in9/11/20139/12/20139/12/2013 10:38:40 AMAPART
Inspection for hanger attatchments above the sheetrock lid in the three new rooms at the production area okayed for cover. Also completed rough-in for the new and relocated uprights due to wall construction.
FIR13-00424 INSP-Final Inspection9/11/20139/12/20139/12/2013 10:34:47 AMAPART
Okay to cover overhead fire sprinkler work at the grid ceilings in the tenant remodel area.