BLD14-01229
| FIRE-Final Inspection | 9/11/2014 | 9/12/2014 | 9/12/2014 1:26:22 PM | A | PASS |
|
|
Life safety passed
|
BLD14-00621
| FIRE-Final Inspection | 9/12/2014 | 9/12/2014 | 9/12/2014 1:02:28 PM | P | PASS |
|
|
Life safety passed
|
FIR14-00425
| INSP-Final Inspection | 9/12/2014 | 9/12/2014 | 9/12/2014 12:58:22 PM | P | PASS |
|
|
Permit finaled
|
FIR13-00723
| INSP-Final Inspection | 9/11/2014 | 9/12/2014 | 9/12/2014 12:05:25 PM | A | FAIL |
|
|
New hanger work is complete. Need the existing building work completed. Need electric alarm bell installed. Forward flush did not pass. Need backflow certified.
|
FIR14-00095
| INSP-Final Inspection | 9/11/2014 | 9/12/2014 | 9/12/2014 12:03:24 PM | A | FAIL |
|
|
Items test today included tamper switches for the backflow, hose valve and new hanger riser. Also included were the new hanger flow switch, smoke, pull, phone lines and loss of a/c. Elevator and riser to existing building is not complete. Need breaker lock and breaker identified. Electric alarm bell not installed yet.
|
FIR14-00199
| INSP-Final Inspection | 9/11/2014 | 9/12/2014 | 9/12/2014 11:58:58 AM | A | PASS |
|
|
Plan modification approved. Permit finaled
|
BLD14-02409
| FIRE-Final Inspection | 9/10/2014 | 9/12/2014 | 9/12/2014 11:58:19 AM | A | FAIL |
|
|
Inspection was actually a conference for life safety requirements. I noted that all exit signs and emergeny lights would need repaired and tested. Some areas may need emergency lights added. One exit sign was missing at the top of the stairs.Door hardware appeared ok as well as the existing fire alarm horn/strobe locations.
|
BLD14-02402
| FIRE-Final Inspection | 9/11/2014 | 9/12/2014 | 9/12/2014 9:47:19 AM | A | PASS |
|
|
Previous corrections addressed. Life safety passed.
|
FIR14-00417
| INSP-Sprinkler Rough-in | 9/11/2014 | 9/12/2014 | 9/12/2014 8:40:21 AM | A | PASS |
|
|
Rough-in passed. Piping can not be covered until a tenting inspection has been performed
|