BLD16-03277
| FIRE-Final Inspection | 9/9/2016 | 9/12/2016 | 9/12/2016 4:23:37 PM | A | PASS |
|
|
Previously noted items have been addressed, emergency egress lighting/exit signage has been repaired, trouble on fire panel is due to a "Cable Tamper" on the anti-freeze loop (Anti-freeze loop valves are open with and anti-freeze solution is reported at -10 on the inspection tag), spoke with hired contractor, Fidel with State Fire Protection, repair is complete and fire panel is showing normal. Fire extinguishers have a current inspection tag but will expire soon, extinguishers will be inspected by a licensed comtractor and tagged accordingly. Final life fire safety inspection for temporary occupancy passed/complete.
|
FIR16-00291
| INSP-Final Inspection | 9/12/2016 | 9/12/2016 | 9/12/2016 3:55:14 PM | P | PART |
|
|
Final fire alarm inspection complete, final items to be tested is the new dry system and associated components.
|
FIR16-00394
| INSP-Alarm Testing | 9/12/2016 | 9/12/2016 | 9/12/2016 3:51:45 PM | P | DONE |
|
|
Alarm testing complete, items left to test: new preaction fire sprinkler system and associated devices.
|
FIR16-00265
| INSP-Sprinkler Rough-in | 9/9/2016 | 9/12/2016 | 9/12/2016 1:14:44 PM | A | PASS |
|
|
Rough to cover inspection for west side drive through area & the southeast side ramp overhead fire sprinkler piping complete. Overhead fire sprinkler piping located in the west side drive through area & the southeast side ramp approved to cover. Rough to cover inspection for the fire sprinkler piping located above the ceilings in the central waiting/office area for VRT complete, overhead fire sprinkler piping in VRT waiting/office area approved for cover.
|
FIR15-00727
| INSP-Sprinkler Rough-in | 9/9/2016 | 9/12/2016 | 9/12/2016 1:12:22 PM | P | PASS |
|
|
Rough to cover inspection complete for overhead fire sprinkler piping located above the convention center level 2 soffits & hardlids, level 4 ceiling grid area's & hardlids, level 3 dry stsem as well as level 2 dry system, area's inspected for rough to cover inspection approved for cover.
|
FIR16-00439
| INSP-Sprinkler Rough-in | 9/9/2016 | 9/12/2016 | 9/12/2016 1:08:03 PM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping approved for cover. Tenting inspection complete for overhead fire sprinkler piping located in attic spaces, overhead fire sprinkler pipe tenting approved for cover. Fire sprinkler heads in upstairs closets are located less than 24 inches away from heat register (fire sprinkler heads were ordinary temperature heads at time of this inspection). NFPA 13R requires ordinary temperature heads to be 24 inches from edge of heat source, 12 inches away for intermediate temperature heads, (NFPA 13R, Table 6.2.3.3.3) fire sprinkler heads will need to be changed to intermediate temperature and verified before final inspection. Fire sprinkler heads in main entry for all apartments have fire sprinkler heads that are less than 8 feet apart, NFPA 13R specifies a minimum of 8 feet between heads, the on site sprinkler contractor instructed that a surface mount light will be dividing the space between the 2 fire sprinkler heads, noted that distance of light below the deflector of the fire sprinkler head will need to be verified after light fixture is installed, if the light is not an obstruction then fire sprinkler heads will need to be relocated to code compliant of having a minimum of 8 feet between fire sprinkler heads.
|
FIR16-00442
| INSP-Sprinkler Rough-in | 9/9/2016 | 9/12/2016 | 9/12/2016 1:07:45 PM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping approved for cover. Tenting inspection complete for overhead fire sprinkler piping located in attic spaces, overhead fire sprinkler pipe tenting approved for cover. Fire sprinkler heads in upstairs closets are located less than 24 inches away from heat register (fire sprinkler heads were ordinary temperature heads at time of this inspection). NFPA 13R requires ordinary temperature heads to be 24 inches from edge of heat source, 12 inches away for intermediate temperature heads, (NFPA 13R, Table 6.2.3.3.3) fire sprinkler heads will need to be changed to intermediate temperature and verified before final inspection. Fire sprinkler heads in main entry for all apartments have fire sprinkler heads that are less than 8 feet apart, NFPA 13R specifies a minimum of 8 feet between heads, the on site sprinkler contractor instructed that a surface mount light will be dividing the space between the 2 fire sprinkler heads, noted that distance of light below the deflector of the fire sprinkler head will need to be verified after light fixture is installed, if the light is not an obstruction then fire sprinkler heads will need to be relocated to code compliant of having a minimum of 8 feet between fire sprinkler heads.
|
FIR16-00443
| INSP-Sprinkler Rough-in | 9/9/2016 | 9/12/2016 | 9/12/2016 1:07:30 PM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping approved for cover. Tenting inspection complete for overhead fire sprinkler piping located in attic spaces, overhead fire sprinkler pipe tenting approved for cover. Fire sprinkler heads in upstairs closets are located less than 24 inches away from heat register (fire sprinkler heads were ordinary temperature heads at time of this inspection). NFPA 13R requires ordinary temperature heads to be 24 inches from edge of heat source, 12 inches away for intermediate temperature heads, (NFPA 13R, Table 6.2.3.3.3) fire sprinkler heads will need to be changed to intermediate temperature and verified before final inspection. Fire sprinkler heads in main entry for all apartments have fire sprinkler heads that are less than 8 feet apart, NFPA 13R specifies a minimum of 8 feet between heads, the on site sprinkler contractor instructed that a surface mount light will be dividing the space between the 2 fire sprinkler heads, noted that distance of light below the deflector of the fire sprinkler head will need to be verified after light fixture is installed, if the light is not an obstruction then fire sprinkler heads will need to be relocated to code compliant of having a minimum of 8 feet between fire sprinkler heads.
|
BLD16-02323
| FIRE-Final Inspection | 9/11/2016 | 9/12/2016 | 9/12/2016 12:41:14 PM | A | FAIL |
|
|
No fire sprinklers, the building has an active fire alarm panel with a wireless communicator installed, appears that the fire alarm work was completed without a permit or inspection, fire extinguishers were not on site at time of inspection, fire extinguishers will be mounted in discussed locations and will be verified at next inspection. A FIR permit needs to be in issued status before final inspection for the fire alarm system to be completed. Life fire safety for this permit BLD16-02323 will not be finaled until fire alarm issue is resolved.
|
FIR13-00167
| INSP-Sprinkler Rough-in | 9/8/2016 | 9/12/2016 | 9/12/2016 10:48:31 AM | A | CANC |
|
|
Inspection will be performed on a later inspection request, inspection request reshedule has been coordinated with job foreman (Jeff ###-####). Shilo will call to schedule the inspection request for coordinated day.
|
FIR15-00602
| INSP-Sprinkler Rough-in | 9/12/2016 | 9/12/2016 | 9/12/2016 10:44:42 AM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping located on the west side level 1 wing complete, including shell protection for future tenant area, level 1 west wing overhead fire sprinkler piping approved for cover. Rough to cover inspection for overhead fire sprinkler piping located on the north side level 1 lobby area complete, overhead fire sprinkler piping located on north level 1 lobby approved for cover.
|
FIR15-00727
| INSP-Sprinkler Rough-in/Hydro | 9/9/2016 | 9/12/2016 | 9/9/2016 5:06:45 PM | P | CANC |
|
|
Mike Martin is the contact for this inspection. He wanting a rough to cover inspection. Phone #: ###-#### >> Inspection requested via web by Kay Haney Inspection cancelled from web by: Kay Haney
|