Inspections for the day of: Tuesday, September 12, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-02136 Final9/12/20179/12/20179/12/2017 1:18:56 PMPPASS
Garage Code 3688 - Final Re-inspect Phone #: ###-#### Inspection requested via web by Ben Grundhauser Corrections made final ok
ELE17-02972 Rough-In Permanent Service9/11/20179/12/20179/12/2017 12:48:25 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn rough in ok p/s u/g n ok
ELE17-02246 Final9/11/20179/12/20179/12/2017 12:37:06 PMPPASS
Access is 7575 or 8080. Thank you. Phone #: ###-#### Inspection requested via web by Paula Gratiot Corrections made Final ok
ELE17-03011 Temporary Service9/12/20179/12/20179/12/2017 12:33:03 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE17-02467 Electrical Rough-In9/12/20179/12/20179/12/2017 11:35:16 AMAPASS
Phone #: ###-#### Inspection requested via web by Tom Jenkins Office underground to gate and service room ok to cover
ELE17-03005 Conference9/11/20179/12/20179/12/2017 11:34:19 AMADONE
Contact: Brian Gee.. Would like to schedule for 9:00 or 11:00, please call before going Phone #: ###-#### Inspection requested via web by Deb Gooden Met onsite Discussed article 110.26 B. Electrical working space shall not be used for storage. 110.26 C 2. @ Egress paths for services over 1200Amps. 110.26 C 3. Panic hardware on egress doors on services over 800A. 110.26 D. Lighting for service rooms.210.64. Service Receptacle Required. Also discussed removing old exposed romex and "cleaning" up unsafe wiring.
ELE17-01507 Final9/11/20179/12/20179/12/2017 10:32:38 AMAPASS
Everything should be good now, Thank you Phone #: ###-#### Inspection requested via web by Rick Beckman Corrections made final ok
ELE17-02378 Rough-In Permanent Service9/11/20179/12/20179/12/2017 10:17:08 AMAPASS
Phone #: ###-#### Inspection requested via web by Paula Gratiot Rough in OK p/s u/g n ok
ELE17-03016 Temporary Service9/11/20179/12/20179/12/2017 9:46:42 AMAPASS
Phone #: ###-#### Inspection requested via web by Neal Rumsey t/s u/g n ok
ELE17-02220 Electrical Rough-In9/12/20179/12/20179/12/2017 9:33:40 AMAPASS
Mail box building rough cover Phone #: ###-#### Inspection requested via web by Kenneth Chapman ok to cover
ELE17-01718 Final9/11/20179/12/20179/12/2017 9:22:21 AMAFAIL
Phone #: ###-#### Inspection requested via web by John VanZandt 210.8 A 3. All outdoor receps shall be gfci protected. 406.9 A Outdoor receps shall have in use covers.