Inspections for the day of: Wednesday, September 12, 2018.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02598 Final9/12/20189/12/20189/12/2018 5:13:13 PMPFAIL
Phone #: ###-#### Inspection requested via web by Alan Lusk
110.3- Items shall be connected as per manufacturers instructions. Level 3 bath GFI has reverse polarity, Level 1 understair light not working.
210.8- Washer receptacle is located with in 6' of a sink and shall be GFCI protected.
210.12- Level 1 room has closet with clothes rod installed so shall have AFCI protected.
314.20- Where boxes installed in a wall with non combustible materials they shall not be set back more than 1/4" from surface with out box extensions installed. Kitchen counter receptacles.
348.30- FMC shall be secured with in 12" of each box. Disposal
ELE18-01206 Electrical Rough-In9/11/20189/12/20189/12/2018 4:00:03 PMACANC
Please call Chris for inspection of 1st floor walls. As close to 1PM as possible please.

Thanks. Phone #: ###-#### Inspection requested via web by Rafael Castillo
Unable to inspect job prior to crew leaving for the day. Called contact he stated OK would reschedule for next day.
ELE18-02183 Final9/12/20189/12/20189/12/2018 3:57:35 PMPPASS
Please call Ron upon arrival at the 17C lobby. Phone #: ###-#### Inspection requested via web by Ron Pontius
BLDG 15 room 106A build out. South wall added and floor receptacles. All wiring for future tools covered on blanket permit. Final ok
ELE18-03292 Electrical Rough-In9/12/20189/12/20189/12/2018 3:19:47 PMPPASS
We need a wall rough, Tobias is the contact.
Thank you Phone #: ###-#### Inspection requested via web by Stacie Tasker
Walls rough in ok cover
ELE18-03490 Electrical Rough-In9/12/20189/12/20189/12/2018 2:58:28 PMAPASS
Phone #: ###-#### Inspection requested via web by Brad Girard
All areas walls and hardlids rough in ok cover
ELE18-02623 Rough-In Permanent Service9/12/20189/12/20189/12/2018 2:30:51 PMPPASS
ready now Phone #: ###-#### Inspection requested via web by Bob Glenn
Level 3 slider not in place, print shows 3 panel door. If any of the panels are fixed receptacle spacing may be in violation.
Rough in ok cover p/s u/g n ok
ELE18-03488 Temporary Service9/11/20189/12/20189/12/2018 2:10:21 PMAPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson t/s u/g n ok
ELE18-03489 Temporary Service9/11/20189/12/20189/12/2018 2:09:52 PMAPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson t/s u/g n ok
ELE18-03253 Electrical Rough-In9/11/20189/12/20189/12/2018 1:21:29 PMAFAIL
Phone #: ###-#### Inspection requested via web by Wren Van Bockel
110.27- All wiring located below 8' shall be protected from physical damage. Horizontal runs of NM cable shall be protected.
210.8(A)(2)- All 120 volt 15 and 20 amp receptacle outlets located in storage shed shall have GFCI protection.
250.32(B)- All non-current carrying metal parts shall not be connected to grounded conductor on load side of main disconnect. Seperate grounds and neutrals on shed sub panel.
250.64- Grounding electrode conductor shall be terminated at service location. Owner stated was going to have Idaho Power terminate them, informed they will not terminate any other conductors not associated with line side.
300.12- PVC from service to shed shall be a complete system. LB not secured to panel. Reducing washers needed and lock nuts and bushing.
334.30- NM cable shall be secured with in 12" of panel terminations.
ELE17-01337 Final9/11/20189/12/20189/12/2018 12:12:50 PMAPASS
Rescheduled final inspection. Contact is Rick Badley. If possible please notify Rick 30 minutes prior to arriving on site. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Final ok
ELE18-03438 Final9/11/20189/12/20189/12/2018 11:40:16 AMAPASS
Ceiling-Final
Call Dave Forbes ahead of inspection to meet . Phone #: ###-#### Inspection requested via web by Harvey Reyna Final ok
ELE18-03438 Electrical Rough-In9/12/20189/12/20189/12/2018 11:39:54 AMPPASS
Ceiling-Final
Call Dave Forbes ahead of inspection to meet . Phone #: ###-#### Inspection requested via web by Harvey Reyna
Circuits to food coolers and counter out in dining area with portable warmers used. No vending machines installed. Rough in ok cover
ELE18-03493 Permanent Service9/12/20189/12/20189/12/2018 10:46:04 AMPPASS
Contact: Josh Mangum Phone #: ###-#### Inspection requested via web by Deb Gooden
Permit to check out equipment damaged by Knitting Factory damage mostly to mezzanine to offices located above. Electrical room at mezzanine level wet from putting out fire and has branch circuit damage. Contactor to lockout all associated with knitting factory. Idaho power to energize main gear and electrical contractor to verify each tenant space feeders ok prior to energizing. p/s u/g rec ok
ELE18-03201 Final9/11/20189/12/20189/12/2018 8:30:37 AMAPASS
final Phone #: ###-#### Inspection requested via web by David Feller Final ok
ELE18-03201 Electrical Rough-In9/11/20189/12/20189/12/2018 8:29:52 AMAPASS
Re inspection of ceiling Phone #: ###-#### Inspection requested via web by David Feller Grid rough in ok cover