ELE02-02810
| Temporary Service | 9/12/2002 | 9/13/2002 | 9/13/2002 12:00:00 AM | A | PASS |
|
|
justin; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
t/s o/h new ok 9/13/2002 11:46:30 AM
|
ELE02-02779
| Temporary Service | 9/12/2002 | 9/13/2002 | 9/13/2002 12:00:00 AM | A | FAIL |
|
|
calender; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie cor. posted called shall not ID 6or smaller neutral, 250.28 bond service enclosure 9/13/2002 10:41:02 AM
|
ELE02-02857
| Electrical Rough-In | 9/12/2002 | 9/13/2002 | 9/13/2002 12:00:00 AM | A | FAIL |
|
|
###-#### called left message job not ready 300.4 ,nail plates and 11/4, make up not done, strap all mc as code states, what kind of doctors office is it ? does artical 517 apply 9/13/2002 11:37:11 AM
|
ELE02-02841
| Rough-In Permanent Service | 9/12/2002 | 9/13/2002 | 9/13/2002 12:00:00 AM | A | PASS |
|
|
###-#### r/i ok