FIR02-00310
| INSP-Final Inspection | 9/12/2002 | 9/13/2002 | 9/13/2002 12:00:00 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung not a final inspection see flush for this date 9/13/2002 1:40:39 PM
|
MIS02-00216
| FIR-Final | 9/12/2002 | 9/13/2002 | 9/13/2002 12:00:00 AM | A | PASS |
|
|
TERESA ###-####
|
MIS02-00218
| FIR-Final | 9/12/2002 | 9/13/2002 | 9/13/2002 12:00:00 AM | A | PASS |
|
|
TERESA ###-####
|
MIS02-00219
| FIR-Final | 9/12/2002 | 9/13/2002 | 9/13/2002 12:00:00 AM | A | PASS |
|
|
TERESA ###-####
|
MIS02-00220
| FIR-Final | 9/12/2002 | 9/13/2002 | 9/13/2002 12:00:00 AM | A | PASS |
|
|
TERESA ###-####
|
MIS02-00221
| FIR-Final | 9/12/2002 | 9/13/2002 | 9/13/2002 12:00:00 AM | A | PASS |
|
|
TERESA ###-####
|
MIS02-00222
| FIR-Final | 9/12/2002 | 9/13/2002 | 9/13/2002 12:00:00 AM | A | PASS |
|
|
TERESA ###-####
|
MIS02-00223
| FIR-Final | 9/12/2002 | 9/13/2002 | 9/13/2002 12:00:00 AM | A | PASS |
|
|
TERESA ###-#### suite 207 on door; there isn't a suite 210 in the building 9/13/2002 9:38:44 AM
|
FIR02-00310
| INSP-Supply line flush | 9/13/2002 | 9/13/2002 | 9/13/2002 12:00:00 AM | P | PART |
|
|
flushed underground and hydro okay for underground; attempted to forward flow the backflow preventer - couldn't get the required gpm's with the equipment on hand
|
FIR02-00272
| INSP-Sprinkler Rough-in | 9/13/2002 | 9/13/2002 | 9/13/2002 12:00:00 AM | P | PART |
|
|
underground completed to basement wall; depth of bury will be 3 ft where it passes from exterior wall to basement wall; will need to flush and hydro
|
FIR01-00504
| INSP-Final Inspection | 9/11/2002 | 9/13/2002 | 9/13/2002 12:00:00 AM | P | FAIL |
|
|
###-#### attempted hydro on all systems; numerous leaks; will try again next week 9/16/2002 8:34:35 AM
|