Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00690 INSP-Final Inspection8/31/20049/13/20049/13/2004 12:00:00 AMAFAIL
###-#### - cliff Need correct sized batteries for panel on 6th floor; need breaker location on all panels and lockout on breaker; point 45 not used as FACP area has two detectors in area; need descriptors for "modules" to indicate location; remote annunciator not installed permanently in front desk area; tested devices in hallways/closets on 2-6 floors; need to test kitchen hood; sprinkler devices, heat detectors in laundry, drops on NAC's as 14 gauge wire is used, penthouse pre-action troubles/alarm, duct detectors, and sounder base devices in rooms and notification in all areas 9/13/2004 11:46:31 AM
FIR04-00237 INSP-Sprinkler Rough-in9/10/20049/13/20049/13/2004 12:00:00 AMAPART
Contact: Chris - Would like at 8 am - Please call to confirm; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Okay to cover; the 2inch main was modified to get around the duct work; head not installed at beam/ductwork in SW corner 9/13/2004 11:35:48 AM
FIR04-00491 INSP-Final Inspection9/13/20049/13/20049/13/2004 12:00:00 AMPPASS
contact: Matt - call to confirm time to meet; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley