MIS05-00149
| FIR-Final | 9/12/2005 | 9/13/2005 | 9/13/2005 3:35:45 PM | A | FAIL |
|
|
Provide and install fire extinguishers as discussed, provide current annual inspection on fire sprinkler system, remove manual flush bolts at restroom doors, provide ADA hardware at back storeroom door south, remove latch hardware at breakroom door.
|
FIR05-00472
| INSP-Final Inspection | 9/12/2005 | 9/13/2005 | 9/13/2005 3:28:37 PM | P | FAIL |
|
|
Provide cut sheet for smoke detector at FACP to determine wall mounted listing, provide sign at door to FACP room, zone 18 and 19 tampers report as waterflow, provide updated map with matching addressing at panel, verify lock and label at breaker to FACP, need sprinkler contractor to facilitate testing of flow switches, pump run, phase reversal etc., still need to test four duct smoke detectors, no access provided at this inspection.
|
BLD04-01909
| FIRE-Final Inspection | 9/12/2005 | 9/13/2005 | 9/13/2005 11:09:34 AM | A | PASS |
|
|
ADA hardware at the previously noted locations has been installed, fire life safety finaled.
|
BLD05-02390
| FIRE-Final Inspection | 9/12/2005 | 9/13/2005 | 9/13/2005 11:06:17 AM | A | PART |
|
|
No final until associated fire alarm and fire sprinkler permits have been reviewed and inspected. Witnessed functionality and location of alarm devices today per agreement from Sam Rogers. Also noted that one sprinkler is overspaced at 140 sq. ft.
|
BLD05-01768
| FIRE-Final Inspection | 9/12/2005 | 9/13/2005 | 9/13/2005 11:00:09 AM | A | PASS |
|
|
Fire life safety finaled.
|
BLD05-00225
| FIRE-Final Inspection | 9/12/2005 | 9/13/2005 | 9/13/2005 10:59:14 AM | A | FAIL |
|
|
Install fire extinguisher on the wall second floor, remove temporary walls, mount fire extinguishers for first floor area.
|
FIR05-00066
| INSP-Final Inspection | 9/12/2005 | 9/13/2005 | 9/13/2005 10:56:34 AM | A | PASS |
|
|
Fire sprinkler passed inspection, permit finaled.
|
FIR05-00080
| INSP-Alarm Testing | 9/12/2005 | 9/13/2005 | 9/13/2005 10:55:36 AM | A | FAIL |
|
|
Resubmitt plans reflecting correct device addressing, duct detector #46 failed to shut down upon smoke detection.
|
FIR05-00379
| INSP-Alarm Testing | 9/12/2005 | 9/13/2005 | 9/13/2005 10:41:31 AM | A | PASS |
|
|
Fire alarm passed inspection.
|