Inspections for the day of: Tuesday, September 13, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS05-00149 FIR-Final9/12/20059/13/20059/13/2005 3:35:45 PMAFAIL
Provide and install fire extinguishers as discussed, provide current annual inspection on fire sprinkler system, remove manual flush bolts at restroom doors, provide ADA hardware at back storeroom door south, remove latch hardware at breakroom door.
FIR05-00472 INSP-Final Inspection9/12/20059/13/20059/13/2005 3:28:37 PMPFAIL
Provide cut sheet for smoke detector at FACP to determine wall mounted listing, provide sign at door to FACP room, zone 18 and 19 tampers report as waterflow, provide updated map with matching addressing at panel, verify lock and label at breaker to FACP, need sprinkler contractor to facilitate testing of flow switches, pump run, phase reversal etc., still need to test four duct smoke detectors, no access provided at this inspection.
BLD04-01909 FIRE-Final Inspection9/12/20059/13/20059/13/2005 11:09:34 AMAPASS
ADA hardware at the previously noted locations has been installed, fire life safety finaled.
BLD05-02390 FIRE-Final Inspection9/12/20059/13/20059/13/2005 11:06:17 AMAPART
No final until associated fire alarm and fire sprinkler permits have been reviewed and inspected. Witnessed functionality and location of alarm devices today per agreement from Sam Rogers. Also noted that one sprinkler is overspaced at 140 sq. ft.
BLD05-01768 FIRE-Final Inspection9/12/20059/13/20059/13/2005 11:00:09 AMAPASS
Fire life safety finaled.
BLD05-00225 FIRE-Final Inspection9/12/20059/13/20059/13/2005 10:59:14 AMAFAIL
Install fire extinguisher on the wall second floor, remove temporary walls, mount fire extinguishers for first floor area.
FIR05-00066 INSP-Final Inspection9/12/20059/13/20059/13/2005 10:56:34 AMAPASS
Fire sprinkler passed inspection, permit finaled.
FIR05-00080 INSP-Alarm Testing9/12/20059/13/20059/13/2005 10:55:36 AMAFAIL
Resubmitt plans reflecting correct device addressing, duct detector #46 failed to shut down upon smoke detection.
FIR05-00379 INSP-Alarm Testing9/12/20059/13/20059/13/2005 10:41:31 AMAPASS
Fire alarm passed inspection.