FIR04-00004
| INSP-Conference | 8/17/2005 | 9/6/2005 | | P | |
|
|
Follow up for inspection
|
FIR05-00514
| INSP-Sprinkler Rough-in | 9/12/2005 | 9/13/2005 | 9/14/2005 8:30:28 AM | P | PART |
|
|
Sprinkler piping in the office area is ok to cover
|
BLD05-00355
| FIRE-Final Inspection | 9/13/2005 | 9/13/2005 | 9/13/2005 4:06:36 PM | P | PART |
|
|
A temporary occupancy was given until the fire alarm permit is finaled
|
FIR05-00407
| INSP-Final Inspection | 9/12/2005 | 9/13/2005 | 9/13/2005 4:04:28 PM | P | PART |
|
|
Tested all fire smoke dampers which functioned correctly. Need to resubmit plans showing the four additional duct detectors required. Need signage on fire alarm room door.
|
FIR05-00515
| INSP-Sprinkler Rough-in/Hydro | 9/12/2005 | 9/13/2005 | 9/13/2005 3:24:28 PM | P | PART |
|
|
Office area sprinkler piping is ok to cover. Still need uprights installed along tenant separation wall and the riser tagged. Wrong SIN number for pendants but per bill no need to resubmit.
|
FIR02-00290
| FIR-Aging Inspection | 9/13/2005 | 9/13/2005 | 9/13/2005 12:28:15 PM | | NR |
|
|
I spoke to Ron Hagen with Sletten Companies about getting these permits finaled. He gave me the building owner, Allen Lindstrom, phone number where I left a message with a lady. She stated he would call me back today.
|
MIS05-00147
| FIR-Final | 9/12/2005 | 9/13/2005 | 9/13/2005 11:40:45 AM | A | FAIL |
|
|
dru; Phone #: ###-#### Provide "Door to remain unlocked when building is occupied" sticker at the main exit. Repair all exit signs. Provide emergency lights at the exit signs. Provide exit sign as shown on the plans at door between warehouse and office. Provide additional emergency light at the south stairs. Provide address letters that are 4" minimum in height.
|
BLD05-02212
| FIRE-Final Inspection | 9/12/2005 | 9/13/2005 | 9/13/2005 10:21:09 AM | A | PASS |
|
|
Fire life safety finaled
|