Inspections for the day of: Tuesday, September 13, 2005.
Number of inspections: 8
Percentage of inspections complete: 88 %
Percentage of inspections not complete: 13 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00004 INSP-Conference8/17/20059/6/2005 P 
Follow up for inspection
FIR05-00514 INSP-Sprinkler Rough-in9/12/20059/13/20059/14/2005 8:30:28 AMPPART
Sprinkler piping in the office area is ok to cover
BLD05-00355 FIRE-Final Inspection9/13/20059/13/20059/13/2005 4:06:36 PMPPART
A temporary occupancy was given until the fire alarm permit is finaled
FIR05-00407 INSP-Final Inspection9/12/20059/13/20059/13/2005 4:04:28 PMPPART
Tested all fire smoke dampers which functioned correctly. Need to resubmit plans showing the four additional duct detectors required. Need signage on fire alarm room door.
FIR05-00515 INSP-Sprinkler Rough-in/Hydro9/12/20059/13/20059/13/2005 3:24:28 PMPPART
Office area sprinkler piping is ok to cover. Still need uprights installed along tenant separation wall and the riser tagged. Wrong SIN number for pendants but per bill no need to resubmit.
FIR02-00290 FIR-Aging Inspection9/13/20059/13/20059/13/2005 12:28:15 PM NR
I spoke to Ron Hagen with Sletten Companies about getting these permits finaled. He gave me the building owner, Allen Lindstrom, phone number where I left a message with a lady. She stated he would call me back today.
MIS05-00147 FIR-Final9/12/20059/13/20059/13/2005 11:40:45 AMAFAIL
dru; Phone #: ###-####
Provide "Door to remain unlocked when building is occupied" sticker at the main exit. Repair all exit signs. Provide emergency lights at the exit signs. Provide exit sign as shown on the plans at door between warehouse and office. Provide additional emergency light at the south stairs. Provide address letters that are 4" minimum in height.
BLD05-02212 FIRE-Final Inspection9/12/20059/13/20059/13/2005 10:21:09 AMAPASS
Fire life safety finaled