Inspections for the day of: Wednesday, September 13, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01297 ELE-Aging Inspection9/13/20069/13/20069/15/2006 10:07:44 AM NR
wall sign only done, monument not done
ELE06-03179 Final9/12/20069/13/20069/13/2006 4:24:17 PMPFAIL
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, left message, told to call inspector, asking for final, ri not given yet, need to look at x-ray equipment, is metal piping installed? Are violations present? Will need to meet contractor at job. Left correction notice from failed ri inspection request as posted.
ELE06-03017 Final9/13/20069/13/20069/13/2006 4:18:06 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Zane Robertson ok to final
ELE06-02254 Electrical Rough-In9/13/20069/13/20069/13/2006 3:14:28 PMPPART
Scheduled by a contractor via Hello! on 9/13/2006 at 10:08:24 AM. Contact: ###-####. south 1/2 u/g ok to cover at front bldg
ELE06-03231 Electrical Rough-In9/12/20069/13/20069/13/2006 3:10:24 PMPPASS
Ufer ground inspection - late afternoon, if possible. Thanks.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok to pour gec
ELE06-03408 Electrical Rough-In9/13/20069/13/20069/13/2006 3:09:30 PMPFAIL
Request for cieling inspectoin. Building is occupied; Phone #: ###-#### Internet Inspection Request from: Nikki Day called left corr notice, nec 300.4(D) edge of mc cable shall be 1 1/4" from edge of framing member, 300.30(B) mc cable shall be secured within 12" of box, 110.12(A) unused openings in box shall be closed, 725.3(B) abandoned cl2 and cl3 cable shall be removed, BCC lv wiring shall not use grid as support, no violations shall be retained
ELE06-00117 Electrical Rough-In9/13/20069/13/20069/13/2006 2:01:41 PMPPASS
mike - ceiling insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover ceiling
ELE06-03271 Final9/13/20069/13/20069/13/2006 1:29:57 PMPPASS
john- call prior for access (early afternoon if possible) ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
ELE06-02919 Final9/13/20069/13/20069/13/2006 1:29:18 PMPPASS
finished by ele 06-03411, ok to final
ELE06-03411 Final9/13/20069/13/20069/13/2006 1:26:55 PMPPASS
scott; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
ELE06-02021 Final9/12/20069/13/20069/13/2006 12:06:02 PMACANC
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS called talked to elect, he must call for core and shell final before ti can be finalled
ELE06-03405 Rough-In Permanent Service9/12/20069/13/20069/13/2006 12:04:56 PMAFAIL
jim; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 334.30 nm cable shall not be stapled on edge, 314.20 boxes shall be flush with finished surface, 250.64(D) gec shall be tapped outside box, not run thru, 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing member, BCC job id sticker shall be posted, approved set of plans on job(done)
ELE06-03401 Rough-In Permanent Service9/12/20069/13/20069/13/2006 10:43:17 AMAPASS
ron; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ric ok both sides, saw gec both, ok power to west side only, p/s u/g n ok
ELE06-03402 Final9/12/20069/13/20069/13/2006 9:21:35 AMAPASS
Suite 104 / Maryland; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz ok to final
ELE06-00113 Final9/12/20069/13/20069/13/2006 9:00:15 AMAPART
Contact Greg Pack. Final inspection for 6th floor rooms.; Phone #: ###-#### Internet Inspection Request from: Shelli Daylong 6th fl rooms only except 610, ok to final, anop, check heater breakers, access hole for tub