ELE06-01297
| ELE-Aging Inspection | 9/13/2006 | 9/13/2006 | 9/15/2006 10:07:44 AM | | NR |
|
|
wall sign only done, monument not done
|
ELE06-03179
| Final | 9/12/2006 | 9/13/2006 | 9/13/2006 4:24:17 PM | P | FAIL |
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, left message, told to call inspector, asking for final, ri not given yet, need to look at x-ray equipment, is metal piping installed? Are violations present? Will need to meet contractor at job. Left correction notice from failed ri inspection request as posted.
|
ELE06-03017
| Final | 9/13/2006 | 9/13/2006 | 9/13/2006 4:18:06 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Zane Robertson ok to final
|
ELE06-02254
| Electrical Rough-In | 9/13/2006 | 9/13/2006 | 9/13/2006 3:14:28 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 9/13/2006 at 10:08:24 AM. Contact: ###-####. south 1/2 u/g ok to cover at front bldg
|
ELE06-03231
| Electrical Rough-In | 9/12/2006 | 9/13/2006 | 9/13/2006 3:10:24 PM | P | PASS |
|
|
Ufer ground inspection - late afternoon, if possible. Thanks.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok to pour gec
|
ELE06-03408
| Electrical Rough-In | 9/13/2006 | 9/13/2006 | 9/13/2006 3:09:30 PM | P | FAIL |
|
|
Request for cieling inspectoin. Building is occupied; Phone #: ###-#### Internet Inspection Request from: Nikki Day called left corr notice, nec 300.4(D) edge of mc cable shall be 1 1/4" from edge of framing member, 300.30(B) mc cable shall be secured within 12" of box, 110.12(A) unused openings in box shall be closed, 725.3(B) abandoned cl2 and cl3 cable shall be removed, BCC lv wiring shall not use grid as support, no violations shall be retained
|
ELE06-00117
| Electrical Rough-In | 9/13/2006 | 9/13/2006 | 9/13/2006 2:01:41 PM | P | PASS |
|
|
mike - ceiling insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover ceiling
|
ELE06-03271
| Final | 9/13/2006 | 9/13/2006 | 9/13/2006 1:29:57 PM | P | PASS |
|
|
john- call prior for access (early afternoon if possible) ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
|
ELE06-02919
| Final | 9/13/2006 | 9/13/2006 | 9/13/2006 1:29:18 PM | P | PASS |
|
|
finished by ele 06-03411, ok to final
|
ELE06-03411
| Final | 9/13/2006 | 9/13/2006 | 9/13/2006 1:26:55 PM | P | PASS |
|
|
scott; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
|
ELE06-02021
| Final | 9/12/2006 | 9/13/2006 | 9/13/2006 12:06:02 PM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS called talked to elect, he must call for core and shell final before ti can be finalled
|
ELE06-03405
| Rough-In Permanent Service | 9/12/2006 | 9/13/2006 | 9/13/2006 12:04:56 PM | A | FAIL |
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 334.30 nm cable shall not be stapled on edge, 314.20 boxes shall be flush with finished surface, 250.64(D) gec shall be tapped outside box, not run thru, 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing member, BCC job id sticker shall be posted, approved set of plans on job(done)
|
ELE06-03401
| Rough-In Permanent Service | 9/12/2006 | 9/13/2006 | 9/13/2006 10:43:17 AM | A | PASS |
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ric ok both sides, saw gec both, ok power to west side only, p/s u/g n ok
|
ELE06-03402
| Final | 9/12/2006 | 9/13/2006 | 9/13/2006 9:21:35 AM | A | PASS |
|
|
Suite 104 / Maryland; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz ok to final
|
ELE06-00113
| Final | 9/12/2006 | 9/13/2006 | 9/13/2006 9:00:15 AM | A | PART |
|
|
Contact Greg Pack. Final inspection for 6th floor rooms.; Phone #: ###-#### Internet Inspection Request from: Shelli Daylong 6th fl rooms only except 610, ok to final, anop, check heater breakers, access hole for tub
|