Inspections for the day of: Wednesday, September 13, 2006.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-01063 FIRE-Final Inspection9/13/20069/13/20069/15/2006 12:19:47 PMPPART
A temporary occupancy was given until the phase II (remodeled existing area) is complete. The new FMC building is complete.
FIR05-00693 INSP-Final Inspection9/13/20069/13/20069/15/2006 12:18:36 PMPPART
A temporary occupancy was given until the phase II (remodeled existing area) is complete. The new FMC building is complete.
FIR05-00801 INSP-Alarm Testing9/13/20069/13/20069/15/2006 12:13:15 PMPPART
A temporary occupancy was given for the basement mech. room. A/v's have been tested, smoke detectors and the sprinkler control valves for this same areas sprinkler system. The fire pump and related items are not ready yet.
FIR06-00165 INSP-Final Inspection9/12/20069/13/20069/13/2006 3:56:16 PMPPASS
permit finaled
BLD05-02403 FIRE-Final Inspection9/13/20069/13/20069/13/2006 3:54:57 PMPPASS
Life safety finaled.
BLD03-00590 FIRE-Final Inspection9/12/20069/13/20069/13/2006 11:52:40 AMAPASS
Life safety finaled
FIR06-00137 INSP-Sprinkler Rough-in9/12/20069/13/20069/13/2006 11:52:15 AMAPASS
Underground supply piping is ok to cover. Size of underground installed is 4". 6" is shown on the plans.
FIR06-00168 INSP-Sprinkler Rough-in9/13/20069/13/20069/13/2006 10:54:03 AMPCANC
todd; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley Inspection cancelled from web by: Alicia Pauley
FIR05-00799 INSP-Alarm Testing9/13/20069/13/20069/13/2006 10:32:25 AMAFAIL
The a/v's need to be exchanged in the ICU area and the nomanclature needs to be changed at the riser room devices as discussed. All other items on the correction notice have been corrected.
FIR06-00566 INSP-Final Inspection9/12/20069/13/20069/13/2006 10:22:59 AMAFAIL
All of the a/v's are mounted too low and the 15cd strobe in the records area is overspaced.
FIR06-00011 INSP-Alarm Testing9/13/20069/13/20069/13/2006 6:41:59 AMPCANC
Scheduled by a contractor via Hello! on 9/13/2006 at 4:53:13 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Sep 13 2006 6:41AM.