Inspections for the day of: Thursday, September 13, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01438 Electrical Rough-In9/12/20079/13/20079/13/2007 4:07:21 PMPCANC
daniel Note: please call 1/2 hr prior to open the bldg Phone #: ###-#### called contr will reschedule and call me
ELE07-03194 Temporary Service9/13/20079/13/20079/13/2007 4:00:17 PMPPASS
darin Phone #: ###-#### t/s u/g new ok
ELE07-03193 Electrical Rough-In9/13/20079/13/20079/13/2007 3:38:19 PMPPASS
rocky - ok to cover Phone #: ok
ELE07-03080 Electrical Rough-In9/13/20079/13/20079/13/2007 2:58:53 PMPPASS
J R; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok
ELE07-03180 Temporary Service9/12/20079/13/20079/13/2007 2:27:29 PMAPASS
Thanks
Dan Phone #: ###-#### Internet Inspection Request from: Dan Rohl t/s u/g new ok
ELE07-02099 Final9/13/20079/13/20079/13/2007 2:11:30 PMPPASS
Please call property manager, Jason, @ ###-#### to meet you there with keys. Thank you. Phone #: ###-#### Internet Inspection Request from: Carla Ward ok
ELE07-01796 Final9/13/20079/13/20079/13/2007 2:11:12 PMPPASS
Please call property manager, Jason @ ###-#### so he can meet you there with keys. Phone #: ###-#### Internet Inspection Request from: Carla Ward ok
ELE07-02673 Electrical Rough-In9/13/20079/13/20079/13/2007 1:36:51 PMPFAIL
safet Phone #: ###-#### corr met owner needs nail plated outside of holes 300.4(A)(1) 220 needs service calcs also owner wired hot tub without permit or inspection owner needs to update permit for 7rms and p/s if he changes out to a larger size
ELE07-03183 Electrical Rough-In9/12/20079/13/20079/13/2007 12:14:36 PMAPART
please call Tim Watkins with any questions Phone #: ###-#### x0000 Internet Inspection Request from: Sandee Johnson
walls ok called nail plates for ent ,also secure within 3ft of boxes, and re ID white in cable 200.7
ELE07-03120 Rough-In Permanent Service9/12/20079/13/20079/13/2007 11:12:45 AMAFAIL
Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson
permit and addresses all messed up
ELE07-03101 Electrical Rough-In9/12/20079/13/20079/13/2007 10:15:57 AMAFAIL
Matt is the Journeyman for this job. Cabinet layout is in window and prints are under it, in the wall. Phone #: ###-#### Internet Inspection Request from: chris green
corr. fee due , do not cover called, 300.4(A)(1) nail plates, 314.16 box fill, 314.43 screws not allowed in plastic boxes, 210.52(C) pantry shall be on small appliance brach circuit, note if island not flat acorr entire surface outlets not allowed below countertop size GEC to water for to table 250.66 needs #2 copper use plastic or listed metal conn for GEC terminat GEC within