Inspections for the day of: Thursday, September 13, 2007.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03148 Electrical Rough-In9/13/20079/13/20079/13/2007 4:26:36 PMPPASS
Pat Thomas, Electrician ###-#### on site, need ruff-in this pm.
Phone #: ###-#### Internet Inspection Request from: BRENDA HURST ric ok
ELE07-03148 Final9/13/20079/13/20079/13/2007 4:20:50 PMPPASS
Pat Thomas, Electrician ###-#### on site, need ruff-in this pm.
Phone #: ###-#### Internet Inspection Request from: BRENDA HURST ok to final
ELE07-01468 Electrical Rough-In9/13/20079/13/20079/13/2007 4:07:02 PMPPASS
raina - trench Phone #: ###-#### u/g only ok to cover from house to new garage
ELE07-03163 Electrical Rough-In9/11/20079/13/20079/13/2007 3:27:37 PMPPASS
Roger ###-####; changed inspection time for 9/13 per customer ric ok -remodel, basement only
ELE07-03153 Conference9/12/20079/13/20079/13/2007 2:46:18 PMPDONE
John, call 30 minutes prior; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt met owner, talked about new service, timing for change-over, grounding, and underground
ELE07-03189 Permanent Service9/13/20079/13/20079/13/2007 2:17:36 PMPPASS
Phone #: ###-#### Internet Inspection Request from: BRENDA HURST p/s u/g n ok, address looks like nez perce
ELE07-03188 Electrical Rough-In9/13/20079/13/20079/13/2007 1:56:31 PMPPASS
terry Phone #: ###-#### called contractor, told no u/g from house to garage seen, flush out box for door lite, ric ok, they will call for u/g inspection, no grounding electrode seen
ELE07-03190 Permanent Service9/13/20079/13/20079/13/2007 1:33:58 PMPPASS
Phone #: ###-#### Internet Inspection Request from: BRENDA HURST p/s u/g n ok, address looks like nez perce
ELE07-03169 Rough-In Permanent Service9/13/20079/13/20079/13/2007 1:18:54 PMPPASS
Daryl; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ric ok, p/s u/g n ok, u/g to sub-panel ok garage to house
ELE07-03039 Final9/12/20079/13/20079/13/2007 10:44:35 AMAPASS
louis Phone #: ###-#### ok to final
ELE07-02724 Rough-In Permanent Service9/12/20079/13/20079/13/2007 9:58:36 AMACANC
Scheduled by a contractor via Hello! on 9/12/2007 at 1:01:31 PM. Contact: ###-####. see ri and p/s
ELE07-02724 Electrical Rough-In9/13/20079/13/20079/13/2007 9:58:14 AMPFAIL
Scheduled by a contractor via Hello! on 9/12/2007 at 1:01:31 PM. Contact: ###-####. called contr, left corr notice: nec 300.4 edge of bored holes shall be 1 1/4" from edge of framing members, 348.30(A) fmc shall be strapped within 12" of panels, 110.26(F)(1)(b) ducts over dedicated panel space shall have drip protection, 348.42 angle connectors shall not be used for concealed raceway installations, BCC inspection of raceways shall be made before cover
ELE07-02724 Permanent Service9/13/20079/13/20079/13/2007 9:29:30 AMAPASS
Scheduled by a contractor via Hello! on 9/12/2007 at 1:01:31 PM. Contact: ###-####. p/s u/g n ok, 4 meters
ELE07-02724 Electrical Rough-In9/13/20079/13/20079/13/2007 9:27:02 AMACANC
Scheduled by a contractor via Hello! on 9/12/2007 at 1:01:31 PM. Contact: ###-####. cloned wrong permit
ELE07-03146 Final9/12/20079/13/20079/13/2007 8:49:08 AMAPASS
Phone #: ###-#### Internet Inspection Request from: BRENDA HURST called contr, told to call for ri before final, told he needs to update panel schedules, and add breaker closures for lp4, ok to final
ELE07-03182 Temporary Service9/13/20079/13/20079/13/2007 8:14:10 AMAPASS
t/s u/g n ok
ELE07-03181 Temporary Service9/12/20079/13/20079/13/2007 8:13:12 AMAPASS
temp power Phone #: ###-#### Internet Inspection Request from: Therrin Robertson t/s u/g n ok
ELE07-03182 Final9/12/20079/13/20079/13/2007 8:11:34 AMAPASS
temp power Phone #: ###-#### Internet Inspection Request from: Therrin Robertson t/s u/g n ok
ELE07-03110 Electrical Rough-In9/11/20079/13/20079/12/2007 2:44:06 PMACANC
PARTIAL INSPECTION ONLY: PLEASE INSPECT ALL BUT KITCHEN. GARAGE CODE FOR ACCESS: 5220 CONTACT BOB ###-#### Phone #: ###-#### Internet Inspection Request from: Julie Schroder Inspection cancelled from web by: Julie Schroder