Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00106 INSP-Final Inspection9/12/20079/13/20079/14/2007 10:48:14 AMADEFR
See inspection notes dated 9/13.
FIR07-00316 INSP-Sprinkler Rough-in/Hydro9/12/20079/13/20079/13/2007 4:54:44 PMAFAIL
UG lost 15 psi. at the guage.
BLD06-02542 FIRE-Final Inspection9/13/20079/13/20079/13/2007 4:23:49 PMPPASS
Corrections are complete, fire life safety inspection passed.
BLD07-02366 FIRE-Final Inspection9/13/20079/13/20079/13/2007 3:55:42 PMPPASS
Life safety inspection completed satisfactory.
FIR07-00049 FIR-Aging Inspection9/13/20079/13/20079/13/2007 3:29:31 PM DEFR
Install is not completed for inspection. WIP
FIR07-00236 INSP-Sprinkler Rough-in/Hydro9/12/20079/13/20079/13/2007 3:28:00 PMPPART
OH rough-in is approved for cover, tenting at the second floor is okay, noted missing ball drip at the FDC check, need nailer plates at the second floor feed piping, AG hydro failed due to low start pressure, noted minor field modifications are okay.
FIR07-00235 INSP-Sprinkler Rough-in/Hydro9/12/20079/13/20079/13/2007 3:23:59 PMPFAIL
See approved plans for locations in need of corrections including missing head at the 2nd floor system 2, overspaced head off an adjacent wall 2nd floor syst. 2, tenting at the 3rd floor is NOT adequate, hydro test failed, some DSW have been deleted, the riser and adjacent mech. room are not complete, NOTE: the 2nd floor system 1feed is not connected or has been moved and could not be located-need to verify connection point. Installation is not approved for cover.
FIR07-00544 INSP-Final Inspection9/12/20079/13/20079/13/2007 3:16:02 PMPPASS
Fire sprinkler permit finaled.
FIR07-00617 INSP-Final Inspection9/12/20079/13/20079/13/2007 3:14:11 PMAPART
Nac panel, SD at panel, a/v notification devices tested okay, one cd rating corrected while on site, random check of the duct detectors revealed incorrect sample tubes and non-approved locations, final pending acceptable installation and testing of the duct detectors.