FIR07-00106
| INSP-Final Inspection | 9/12/2007 | 9/13/2007 | 9/14/2007 10:48:14 AM | A | DEFR |
|
|
See inspection notes dated 9/13.
|
FIR07-00316
| INSP-Sprinkler Rough-in/Hydro | 9/12/2007 | 9/13/2007 | 9/13/2007 4:54:44 PM | A | FAIL |
|
|
UG lost 15 psi. at the guage.
|
BLD06-02542
| FIRE-Final Inspection | 9/13/2007 | 9/13/2007 | 9/13/2007 4:23:49 PM | P | PASS |
|
|
Corrections are complete, fire life safety inspection passed.
|
BLD07-02366
| FIRE-Final Inspection | 9/13/2007 | 9/13/2007 | 9/13/2007 3:55:42 PM | P | PASS |
|
|
Life safety inspection completed satisfactory.
|
FIR07-00049
| FIR-Aging Inspection | 9/13/2007 | 9/13/2007 | 9/13/2007 3:29:31 PM | | DEFR |
|
|
Install is not completed for inspection. WIP
|
FIR07-00236
| INSP-Sprinkler Rough-in/Hydro | 9/12/2007 | 9/13/2007 | 9/13/2007 3:28:00 PM | P | PART |
|
|
OH rough-in is approved for cover, tenting at the second floor is okay, noted missing ball drip at the FDC check, need nailer plates at the second floor feed piping, AG hydro failed due to low start pressure, noted minor field modifications are okay.
|
FIR07-00235
| INSP-Sprinkler Rough-in/Hydro | 9/12/2007 | 9/13/2007 | 9/13/2007 3:23:59 PM | P | FAIL |
|
|
See approved plans for locations in need of corrections including missing head at the 2nd floor system 2, overspaced head off an adjacent wall 2nd floor syst. 2, tenting at the 3rd floor is NOT adequate, hydro test failed, some DSW have been deleted, the riser and adjacent mech. room are not complete, NOTE: the 2nd floor system 1feed is not connected or has been moved and could not be located-need to verify connection point. Installation is not approved for cover.
|
FIR07-00544
| INSP-Final Inspection | 9/12/2007 | 9/13/2007 | 9/13/2007 3:16:02 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR07-00617
| INSP-Final Inspection | 9/12/2007 | 9/13/2007 | 9/13/2007 3:14:11 PM | A | PART |
|
|
Nac panel, SD at panel, a/v notification devices tested okay, one cd rating corrected while on site, random check of the duct detectors revealed incorrect sample tubes and non-approved locations, final pending acceptable installation and testing of the duct detectors.
|