Inspections for the day of: Thursday, September 13, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00011 INSP-Alarm Testing9/13/20079/13/20079/14/2007 4:39:56 PMPDONE
See mike timmermans notes for items tested.
FIR06-00811 INSP-Alarm Testing9/13/20079/13/20079/13/2007 4:41:30 PMACANC
Overbooked
FIR07-00707 INSP-Sprinkler Rough-in9/12/20079/13/20079/13/2007 4:39:29 PMPPART
The sprinkler rough-in is ok but the tenting is not done yet. The sprinkler piping can not be covered yet. Plans need to be resubmitted since a sprinkler head has been added in the single head calc area. It appears this area is now the new two head remote area.
FIR07-00511 INSP-Sprinkler Rough-in9/13/20079/13/20079/13/2007 1:38:43 PMPPASS
The mechanical chase in room 143 has been provided a sprinkler head and is ok to cover. The mechanical chase in room 150 is non-combustible and is ok to cover. These are the only two areas inspected.
FIR07-00652 INSP-Alarm Testing9/13/20079/13/20079/13/2007 1:36:52 PMPPASS
Permit finaled
FIR07-00717 INSP-Final Inspection9/12/20079/13/20079/13/2007 1:35:41 PMAPASS
Permit finaled
BLD05-00633 FIRE-Final Inspection9/12/20079/13/20079/13/2007 1:26:23 PMACANC
Need the related fire alarm and fire sprinkler passed first
BLD07-00625 FIRE-Conference9/12/20079/13/20079/13/2007 11:47:49 AMPDONE
The conference was for the roll up fire door. It has been disable and appears to have been connected to the existing simplex fire alarm system due to a relay mounted in the releasing box. The releasing box is not now connected to the door.
FIR07-00758 INSP-Sprinkler Rough-in9/12/20079/13/20079/13/2007 11:13:50 AMAPASS
Rough in for Toley''s coffee passed. Sprinkler piping is ok to cover.
BLD07-01419 FIRE-Final Inspection9/12/20079/13/20079/13/2007 11:11:34 AMAPASS
Life safety passed
FIR07-00130 INSP-Final Inspection9/10/20079/13/20079/13/2007 8:08:03 AMACANC
Cancel due to the fire alarm contractor not calling in his permit. Will need to be rescheduled.
BLD06-01173 FIRE-Final Inspection9/12/20079/13/20079/13/2007 8:06:03 AMACANC
Troy,

I think I have the correct documentation for you to do your inspection. Call me and let me know when you will be at Hillcrest.

Thanks,

Todd Phone #: ###-#### Internet Inspection Request from: Todd Kurns Inspection cancelled from web by: Todd Kurns
FIR07-00534 INSP-Final Inspection9/12/20079/13/20079/13/2007 8:01:39 AMAFAIL
The bell has not been installed yet. No inspection was performed will need to be rescheduled.