BLD10-01246
| FIRE-Final Inspection | 9/13/2010 | 9/13/2010 | 9/13/2010 1:34:19 PM | P | PASS |
|
|
Life safety passed. The building inspector is going to verify the exit discharge lighting.
|
FIR10-00431
| INSP-Final Inspection | 9/13/2010 | 9/13/2010 | 9/13/2010 1:27:12 PM | P | PASS |
|
|
permit finaled
|
FIR10-00430
| INSP-Final Inspection | 9/13/2010 | 9/13/2010 | 9/13/2010 1:22:16 PM | A | PASS |
|
|
permit finaled
|
FIR10-00395
| INSP-Final Inspection | 9/10/2010 | 9/13/2010 | 9/13/2010 1:17:26 PM | A | FAIL |
|
|
The duct smoke detector is being used for fire/smoke damper operation which is outside of the duct smoke detectors listing since it is not listed to 0cfm. I spoke to Randy on site and Mike in the office. No testing was performed.
|
BLD10-01588
| FIRE-Final Inspection | 9/10/2010 | 9/13/2010 | 9/13/2010 11:47:29 AM | A | FAIL |
|
|
Provide correct address and provide single action lever hardware on the doors as marked on the plans as discussed.
|
BLD10-00973
| FIRE-Final Inspection | 9/10/2010 | 9/13/2010 | 9/13/2010 10:53:13 AM | A | PASS |
|
|
Life safety passed.
|
BLD06-02048
| FIRE-Final Inspection | 9/10/2010 | 9/13/2010 | 9/13/2010 10:52:03 AM | A | PASS |
|
|
life safety already passed.
|
BLD10-01246
| FIRE-Final Inspection | 9/10/2010 | 9/13/2010 | 9/13/2010 9:20:57 AM | A | FAIL |
|
|
Provide exit discharge lighting.
|
BLD10-01207
| FIRE-Final Inspection | 9/10/2010 | 9/13/2010 | 9/13/2010 8:51:50 AM | A | PASS |
|
|
life safety passed
|