Inspections for the day of: Friday, September 13, 2013.
Number of inspections: 13
Percentage of inspections complete: 85 %
Percentage of inspections not complete: 15 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00350 INSP-Supply line flush9/5/20139/6/2013 P 
Nate is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
FIR13-00348 INSP-Supply line flush9/5/20139/6/2013 P 
Nate is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
FIR13-00482 INSP-Sprinkler Rough-in9/12/20139/13/20139/16/2013 5:11:49 PMPPART
Final pending repair work at the east side dry system. Scope of permit work is complete.
BLD13-01927 FIRE-Final Inspection9/12/20139/13/20139/16/2013 5:10:27 PMAFAIL
East side fire sprinkler system is not yet in service, fire alarm permit work underway, provide approved hardware at the new warehouse exit door. Project is not yet in condition for final occupancy approval at this time.
FIR13-00494 INSP-Final Inspection9/13/20139/13/20139/16/2013 5:02:40 PMPPART
Okay to cover overhead work. Final pending construction of new soffit and ceiling tile/escutcheons.
FIR13-00288 INSP-Sprinkler Rough-in9/13/20139/13/20139/16/2013 4:55:51 PMPPART
Okay to cover fire sprinkler work at the remainder of grid ceilings in the remodel area (phase 2).
FIR13-00367 INSP-Sprinkler Rough-in9/12/20139/13/20139/16/2013 4:49:40 PMAPART
Inspection for cover completed at the grid ceiling areas- noted two overspaced heads in need of relocation- one at the SE corridor and one adjacent to the west side sheetrock soffit.
BLD13-02193 FIRE-Final Inspection9/12/20139/13/20139/16/2013 2:13:28 PMPPASS
Fire life safety inspection completed satisfactory.
FIR13-00424 INSP-Final Inspection9/13/20139/13/20139/16/2013 7:41:29 AMPPASS
Fire sprinkler permit finaled.
FIR13-00266 INSP-Sprinkler Rough-in9/12/20139/13/20139/13/2013 11:21:37 AMAPART
Remainder of C/N items verified for completion. System two trip tested at 1 min. 6 seconds. System one trip tested at 2 min 15 sec. and will require the addition of a QOD. Quick trip of the new dry valve passed.
FIR13-00451 INSP-Final Inspection9/12/20139/13/20139/13/2013 11:16:48 AMAPASS
Fire alarm work passed functional testing and inspection. Permit final approved.
FIR13-00490 INSP-Sprinkler Rough-in9/12/20139/13/20139/13/2013 11:15:13 AMAPART
Overhead rough-in and modifications to the system at the tenant remodel area okayed for cover.
FIR13-00367 INSP-Final Inspection9/12/20139/13/20139/12/2013 9:49:03 AMACANC
Please call Colton 30 mins prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt