Inspections for the day of: Tuesday, September 13, 2016.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00727 INSP-Sprinkler Rough-in9/9/20169/13/20169/13/2016 5:31:42 PMPCANC
Inspection request will be performed on 14SEPT2016.
FIR13-00167 INSP-Sprinkler Rough-in9/8/20169/13/20169/13/2016 5:30:50 PMACANC
Inspection request will be performed on 14SEPT2016.
BLD16-01895 FIRE-Final Inspection9/12/20169/13/20169/13/2016 12:33:09 PMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is in place and will be getting a current inspection tag. Final life fire safety inspection passed/complete.
BLD15-04281 FIRE-Final Inspection9/12/20169/13/20169/13/2016 11:59:10 AMAPASS
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are in place with current inspection tags, stairs for mezzanine level have been deleted, fire extinguisher designated for mezzanine not required. Final life fire safety inspection passed/complete.
FIR15-00683 INSP-Sprinkler Rough-in9/12/20169/13/20169/13/2016 10:57:38 AMAPASS
Rough-in inspection for overhead fire sprinkler piping complete. Items that will be repaired before final inspection will be the addition of a 286 degree fire sprinkler head on level 1, southeast corridor next to ceiling mount heater unit, heads are overspaced in this area. Multiple fire sprinkler heads on the south fire sprinkler branchline are to close to the metal studs, branchline will be shifted to get sprinkler heads in compliance for spacing from the metal studs. Storage unit on level 2, behind elevator has a fire sprinkler head spaced to far off of wall, head will be relocated to correct spacing issue. All items can be checked during final inspection to verify completion.
FIR15-00683 INSP-Supply line flush9/12/20169/13/20169/13/2016 10:43:00 AMADONE
Underground fire sprinkler main supply flush complete.
FIR16-00088 INSP-Supply line flush9/12/20169/13/20169/13/2016 10:42:19 AMADONE
Underground fire sprinkler main supply flush complete