Inspections for the day of: Tuesday, September 14, 2004.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00543 INSP-Sprinkler Rough-in/Hydro9/13/20049/14/20049/14/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 9/13/2004 at 1:07:18 PM. Contact: ###-####. Okay to cover; will need to check spare heads/escutcheons at final 9/14/2004 11:11:38 AM
FIR04-00453 INSP-Alarm Testing9/14/20049/14/20049/14/2004 12:00:00 AMACANC
dennis ###-#### Rescheduled for 9/16 9/14/2004 3:41:03 PM
BLD00-03428 FIRE-Final Inspection9/14/20049/14/20049/14/2004 12:00:00 AMPFAIL
calvin--exit signs; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Test overhead door release; install exit signs as shown on plans; complete sprinkler tie-in to concourse B and complete hydro test on second floor; remove tape and add escutcheons on all sprinklers; complete rated doors with seals and closures; NFPA 72 record of completion for alarms; provide certificates for sprinkler system and add calc stickers on risers; install signs for auxiliary drains and control valves; certify fire extinguishers 9/14/2004 3:45:36 PM
BLD04-01556 FIRE-Final Inspection9/14/20049/14/20049/14/2004 12:00:00 AMPPASS
odie; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles