Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00064 INSP-Final Inspection9/9/20059/14/20059/14/2005 4:26:36 PMPCANC
Cancel after hours inspection per Mark ###-#### due to a board meeting, he will reschedule for next week.
BLD05-01757 FIRE-Final Inspection9/13/20059/14/20059/14/2005 3:47:17 PMPFAIL
Provide fire extinguisher as discussed, provide tenant address and name at main entry door, verify fire sprinkler system has a current annual inspection, provide emergency lighting and one exit sign as discussed, written on plan, and required in review notes.
MIS05-00142 FIR-Final9/14/20059/14/20059/14/2005 2:32:15 PMPFAIL
Provide the correct suite address and name.
FIR04-00358 INSP-Final Inspection9/14/20059/14/20059/14/2005 2:30:38 PMPPASS
Fire sprinkler permit finaled.
BLD04-00982 FIRE-Final Inspection9/14/20059/14/20059/14/2005 2:29:43 PMPPASS
Code deficient items have been corrected, life safety finaled.
BLD04-01415 FIRE-Final Inspection9/14/20059/14/20059/14/2005 2:28:07 PMPPASS
Correct door hardware has been installed, life safety finaled.
BLD04-02867 FIRE-Final Inspection9/14/20059/14/20059/14/2005 11:42:15 AMAFAIL
The provided fire extinguisher needs a current inspection tag.
FIR04-00724 INSP-Final Inspection9/13/20059/14/20059/14/2005 10:22:33 AMAFAIL
Heads in the mud room do not match temp. ratings, one is 155 and one is 175 degree, provide hydraulic calc. sticker at riser. Note of concern, the combined domestic and fire supply line flush prior to connection at the sprinkler riser was NOT witnessed or requested to be witnessed for verification by an inspector, the system has already been charged, contractor claims a flush was performed by the plumbers, contractor to assume responsibility for any possible contaminants in the system due to non-compliance.
BLD05-01993 FIRE-Conference9/13/20059/14/20059/14/2005 10:01:53 AMADONE
On site confrence to discuss location of an exit sign and emergency lighting in the north stairway.
BLD03-01830 FIRE-Final Inspection9/14/20059/14/20059/14/2005 12:00:00 AMPPART
A smoke door to separate the new breakroom from the exiting corridor was not installed as indicated on the scope of work, contractor says plans do not indicate this door, waiting on clarification from architect in regards to this issue.
FIR05-00461 INSP-Final Inspection9/14/20059/14/20059/14/2005 12:00:00 AMPPASS
Fire sprinkler permit finaled.