Inspections for the day of: Thursday, September 14, 2006.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD06-01125 FIRE-Final Inspection9/14/20069/14/20069/14/2006 3:50:42 PMPPASS
Fire life safety finaled.
FIR06-00489 INSP-Final Inspection9/13/20069/14/20069/14/2006 3:49:29 PMPPASS
Fire alarm inspection passed, permit finaled.
FIR06-00381 INSP-Final Inspection9/11/20069/14/20069/14/2006 3:03:37 PMPPASS
Fire alarm inspection passed, permit finaled.
BLD05-00364 FIRE-Final Inspection9/14/20069/14/20069/14/2006 1:52:55 PMPPASS
Fire life safety is satisfactory, inspection passed.
FIR06-00683 INSP-Sprinkler Rough-in/Hydro9/13/20069/14/20069/14/2006 1:44:38 PMAFAIL
UG fire supply line does not meet the min. depth of bury requirements for freeze protection per NFPA 13. Per plan review notes and this jurisdiction, the min. depth of bury shall be 4'6" from the top of the pipe to finish grade. Several points along the length of pipe as measured are greater than or equal to 1' too shallow.
BLD06-01082 FIRE-Final Inspection9/13/20069/14/20069/14/2006 10:43:14 AMAPASS
Fire life safety passed inspection.
FIR06-00251 INSP-Final Inspection9/13/20069/14/20069/14/2006 9:58:56 AMAPART
Main tie in to new addition is complete, overspacing at north entry has been corrected. Missing ceiling tile and escutcheons at several locations for completion of the remainder of remodeled rooms per scope of work.