Inspections for the day of: Friday, September 14, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00623 INSP-Sprinkler Rough-in9/13/20079/14/20079/17/2007 4:48:25 PMPDEFR
See inspection comments on 9/17.
FIR07-00753 INSP-Final Inspection9/13/20079/14/20079/17/2007 4:47:49 PMPDONE
See inspection comments on 9/17.
BLD07-01440 FIRE-Final Inspection9/13/20079/14/20079/14/2007 4:44:34 PMANR
Pending completion of the project related fire alarm permit work.
FIR07-00617 INSP-Final Inspection9/13/20079/14/20079/14/2007 4:43:10 PMAFAIL
Final pending correct installation of the duct detectors.
FIR07-00316 INSP-Sprinkler Rough-in/Hydro9/14/20079/14/20079/14/2007 4:38:14 PMPFAIL
UG fire supply line hydro failed due to pressure loss at the guage.
FIR07-00695 INSP-Sprinkler Rough-in9/14/20079/14/20079/14/2007 4:36:07 PMPPART
AG install is approved for cover, riser is not yet complete, be aware of possible light fixture obstructions.
BLD07-01725 FIRE-Final Inspection9/13/20079/14/20079/14/2007 4:34:01 PMAPASS
Noted items are complete, fire life safety inspection passed.
FIR07-00638 INSP-Final Inspection9/14/20079/14/20079/14/2007 4:31:07 PMPPASS
Fire sprinkler passed inspection, permit finaled.
FIR07-00652 INSP-Final Inspection9/14/20079/14/20079/14/2007 4:29:59 PMPPASS
Fire alarm permit finaled.
FIR07-00348 INSP-Sprinkler Rough-in/Hydro9/13/20079/14/20079/14/2007 4:24:09 PMAPART
OH install as circled and initialed on the approved plan set for the office storage and computer room areas is approved for cover, need to verify connection to the existing main when complete, hydrostatic test for this area passed although not required per NFPA as the modification is less than 20 heads.
BLD06-03612 FIRE-Final Inspection9/13/20079/14/20079/14/2007 11:19:29 AMAPASS
All items on the previously issued correction notice have been completed, final fire life safety inspection passed.
FIR07-00106 INSP-Sprinkler Rough-in/Hydro9/14/20079/14/20079/14/2007 10:47:29 AMAPART
Verified completion of c/n items at the pump including repair of the pressure limiting device. Ventilation, EM lighting, and floor drain are acceptable. Noted missing outside waterflow bell, need to program weekly run timer/schedule, fire dpt. access road to the pump house is not adequate, the hydrant at the NE corner of the building is not live. Provide a legible copy of the approved plan set at the next inspection for OH rough-in, still need hydrostatic testing.
FIR07-00083 FIR-Aging Inspection9/14/20079/14/20079/14/2007 10:35:22 AM DEFR
Not complete for inspection at this time, work in progress.
BLD06-02547 FIRE-Final Inspection9/13/20079/14/20079/14/2007 10:32:17 AMAPASS
Correction notice items verified for completion, fire life safety passed.