FIR07-00623
| INSP-Sprinkler Rough-in | 9/13/2007 | 9/14/2007 | 9/17/2007 4:48:25 PM | P | DEFR |
|
|
See inspection comments on 9/17.
|
FIR07-00753
| INSP-Final Inspection | 9/13/2007 | 9/14/2007 | 9/17/2007 4:47:49 PM | P | DONE |
|
|
See inspection comments on 9/17.
|
BLD07-01440
| FIRE-Final Inspection | 9/13/2007 | 9/14/2007 | 9/14/2007 4:44:34 PM | A | NR |
|
|
Pending completion of the project related fire alarm permit work.
|
FIR07-00617
| INSP-Final Inspection | 9/13/2007 | 9/14/2007 | 9/14/2007 4:43:10 PM | A | FAIL |
|
|
Final pending correct installation of the duct detectors.
|
FIR07-00316
| INSP-Sprinkler Rough-in/Hydro | 9/14/2007 | 9/14/2007 | 9/14/2007 4:38:14 PM | P | FAIL |
|
|
UG fire supply line hydro failed due to pressure loss at the guage.
|
FIR07-00695
| INSP-Sprinkler Rough-in | 9/14/2007 | 9/14/2007 | 9/14/2007 4:36:07 PM | P | PART |
|
|
AG install is approved for cover, riser is not yet complete, be aware of possible light fixture obstructions.
|
BLD07-01725
| FIRE-Final Inspection | 9/13/2007 | 9/14/2007 | 9/14/2007 4:34:01 PM | A | PASS |
|
|
Noted items are complete, fire life safety inspection passed.
|
FIR07-00638
| INSP-Final Inspection | 9/14/2007 | 9/14/2007 | 9/14/2007 4:31:07 PM | P | PASS |
|
|
Fire sprinkler passed inspection, permit finaled.
|
FIR07-00652
| INSP-Final Inspection | 9/14/2007 | 9/14/2007 | 9/14/2007 4:29:59 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR07-00348
| INSP-Sprinkler Rough-in/Hydro | 9/13/2007 | 9/14/2007 | 9/14/2007 4:24:09 PM | A | PART |
|
|
OH install as circled and initialed on the approved plan set for the office storage and computer room areas is approved for cover, need to verify connection to the existing main when complete, hydrostatic test for this area passed although not required per NFPA as the modification is less than 20 heads.
|
BLD06-03612
| FIRE-Final Inspection | 9/13/2007 | 9/14/2007 | 9/14/2007 11:19:29 AM | A | PASS |
|
|
All items on the previously issued correction notice have been completed, final fire life safety inspection passed.
|
FIR07-00106
| INSP-Sprinkler Rough-in/Hydro | 9/14/2007 | 9/14/2007 | 9/14/2007 10:47:29 AM | A | PART |
|
|
Verified completion of c/n items at the pump including repair of the pressure limiting device. Ventilation, EM lighting, and floor drain are acceptable. Noted missing outside waterflow bell, need to program weekly run timer/schedule, fire dpt. access road to the pump house is not adequate, the hydrant at the NE corner of the building is not live. Provide a legible copy of the approved plan set at the next inspection for OH rough-in, still need hydrostatic testing.
|
FIR07-00083
| FIR-Aging Inspection | 9/14/2007 | 9/14/2007 | 9/14/2007 10:35:22 AM | | DEFR |
|
|
Not complete for inspection at this time, work in progress.
|
BLD06-02547
| FIRE-Final Inspection | 9/13/2007 | 9/14/2007 | 9/14/2007 10:32:17 AM | A | PASS |
|
|
Correction notice items verified for completion, fire life safety passed.
|