Inspections for the day of: Monday, September 14, 2009.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-01115 Electrical Rough-In9/14/20099/14/20099/14/2009 4:17:46 PMPFAIL
Contact: Jeremy Thornock Phone #: ###-#### Internet Inspection Request from: Melissa Kaae called left correction notice, NEC 348.42 shall not use angle connector in concealed ceiling, 348.30(A) fmc shall be securely fastened within 12" of box and every 4 1/2', BCC all make-up shall be done, no esc this project
ELE09-01114 Electrical Rough-In9/14/20099/14/20099/14/2009 4:14:50 PMPFAIL
Contact: Jeremy Thornock Phone #: ###-#### Internet Inspection Request from: Melissa Kaae called left correction notice, NEC 348.42 shall not use angle connector in concealed ceiling, 348.30(A) fmc shall be securely fastened within12" of box and every 4 1/2', BCC all make-up shall be done, no esc this project
ELE09-01113 Electrical Rough-In9/14/20099/14/20099/14/2009 3:57:02 PMPFAIL
Contact: Jeremy Thornock Phone #: ###-#### Internet Inspection Request from: Melissa Kaae called, left correction notice. NEC 348.42 shall not use angle connector in concealed ceiling, 348.30(A) fmc shall be securely fastened within 12" of box and every 4 1/2', BCC all make-up shall be done, no esc this project
ELE09-01112 Electrical Rough-In9/14/20099/14/20099/14/2009 2:36:39 PMPFAIL
Contact: Jeremy Thornock Phone #: ###-#### Internet Inspection Request from: Melissa Kaae called, left correction notice, NEC 348.42 shall not use angle connector in concealed ceiling, 348.30(A) fmc shall be secured witin 12" of box and every 4 1/2', BCC all make-up shall be done, no esc this project
ELE09-01108 Electrical Rough-In9/14/20099/14/20099/14/2009 1:54:40 PMPPASS
Contact: Jeremy Thornock Phone #: ###-#### Internet Inspection Request from: Melissa Kaae corrections made bathrooms only ok to cover, no esc this project
ELE09-01185 Electrical Rough-In9/14/20099/14/20099/14/2009 1:04:02 PMPPASS
Contact: John Stebly - ceiling inspection please Phone #: ###-#### Internet Inspection Request from: Deb Gooden soffits only anop ok to cover, no esc this project
ELE09-00694 Final9/11/20099/14/20099/14/2009 12:05:31 PMAPASS
This is a final inspection please. Contact is Rey. Have a great day! Phone #: ###-#### Internet Inspection Request from: Laura Longshaw corrections made, ok to final, signed occupancy card, no esc this project
ESC09-00342 General Inspection9/14/20099/14/20099/14/2009 9:35:27 AMAPASS
looked ok
ESC09-00422 General Inspection9/14/20099/14/20099/14/2009 9:34:13 AMAPASS
looked ok
ELE09-01455 Final9/11/20099/14/20099/14/2009 9:25:31 AMAPASS
Someone will be home, if you have any questions, please call Clay. Thank You. Phone #: ###-#### Internet Inspection Request from: Clay Morgan met owner, ok to final
ELE09-00903 Final9/11/20099/14/20099/14/2009 8:47:37 AMAPASS
al Phone #: ###-#### met owner, ok to final, no esc this project
ELE09-01722 Permanent Service9/11/20099/14/20099/14/2009 8:09:09 AMAFAIL
Need permanent service & UFER ground inspection. Phone #: ###-#### Internet Inspection Request from: Lloyd Looney called contractor, told corrections, BCC shall clean concrete for gec such that there is no dirt around conductor, ask for re-nspection before pour and to also change guy wires to provide strain support per line tension