Inspections for the day of: Thursday, September 14, 2017.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-03238 FIRE-Final Inspection9/13/20179/14/20179/14/2017 3:11:10 PMAFAIL
Provide emergency lighting as discussed. All other items appear ok.
FIR16-00383 INSP-Alarm Testing9/14/20179/14/20179/14/2017 2:56:44 PMPDONE
Today I verified the panel, batteries, phone lines, phone line troubles, battery troubles and smoke detector over the panel. Most other devices have not been connected to the main fire alarm panel. I was unable to test the hood suppression system and a/v's in the Pizza tenant due to the approved plans for the space not being on site. I also pointed out the a plan modification is needed for the new devices (fire pump) and deletion of devices. Also a plan modification is needed for stair shaft pressurization as noted on the city approved fire alarm plans.
FIR17-00505 INSP-Sprinkler Rough-in/Hydro9/13/20179/14/20179/14/2017 2:37:15 PMPFAIL
Contractor needs to contact plan review and discuss need for as-builts or plan mods due to additional fittings and pipe routing. No tenting is installed. I noted two heads too close to one another. No piping to be covered. Also verification is needed for irrigation piping connection.
BLD17-01362 FIRE-Final Inspection9/13/20179/14/20179/14/2017 2:35:33 PMAPASS
life safety passed
BLD17-00376 FIRE-Final Inspection9/13/20179/14/20179/14/2017 2:09:26 PMAFAIL
Provide small documents, repair the exit discharge light at the main exit, provide panic hardware on both exit doors, possible occupant load signs, tag on the fire extinguisher
FIR17-00280 INSP-Final Inspection9/14/20179/14/20179/14/2017 11:46:04 AMAFAIL
There were no city approved plans on site. No testing performed. Brian is going to provide as-builts for minor changes in this tenant space.
FIR16-00194 INSP-Alarm Testing9/13/20179/14/20179/14/2017 11:44:41 AMAPART
Could not test the fire alarm interconnections due to most of them not being shown on the fire alarm plans. Also appears flow switches and tamper switches have been deleted in the stairwells.
What I was able to do today was trip test both of the dry systems. The first floor had water at the inspectors test in 49 seconds and the second floor was 32 seconds.
FIR17-00334 INSP-Final Inspection9/13/20179/14/20179/14/2017 11:33:46 AMACANC
The fire alarm permit for this interconnect was not ready. No testing was performed.

Dave Phone #: ###-####
BLD17-01721 FIRE-Final Inspection9/14/20179/14/20179/14/2017 8:20:00 AMPPASS
Life safety passed.

Bill Phone #: ###-####
FIR17-00429 INSP-Final Inspection9/13/20179/14/20179/14/2017 8:17:49 AMAPASS
Permit finaled.

Bill Phone #: ###-####
BLD17-01726 FIRE-Final Inspection9/13/20179/14/20179/14/2017 8:15:35 AMAPASS
Life safety passed.

Richard Phone #: ###-####-please call for access
FIR17-00538 INSP-Sprinkler Rough-in9/14/20179/14/20179/14/2017 8:00:38 AMACANC
Contact Brad Westbrook ###-#### 30 min prior to RTC insp Start please.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank