Inspections for the day of: Friday, September 14, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02233 Final9/14/20189/14/20189/14/2018 3:23:39 PMPPASS
Garage code 7573 Phone #: ###-#### Inspection requested via web by Bob Glenn
Will check back in future to ensure hot tub has not been installed in areas in violation of NEC. Final ok
ELE18-02777 Electrical Rough-In9/14/20189/14/20189/14/2018 2:57:23 PMPPASS
Bar rough in inspection Phone #: ###-#### Inspection requested via web by Ryan Wake
Bar wall rough in ok cover
ELE18-03533 Electrical Rough-In9/14/20189/14/20189/14/2018 2:29:37 PMPFAIL
Ron Phone #: ###-####
517.13- Wiring methods in patient care space shall have a effective ground fault current path to all receptacle and switch locations with in patient care space. Confirm all receptacles and the switch in exam room E contain proper wiring method. Did not leave correction on site had verbal with Ron.
ELE18-03199 Rough-In Permanent Service9/14/20189/14/20189/14/2018 1:53:28 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Rough in ok cover p/s u/g n ok
ELE18-03507 Rough-In Permanent Service9/13/20189/14/20189/14/2018 12:43:06 PMAFAIL
call with any questions thank you Phone #: ###-#### Inspection requested via web by kim grundhauser
300.15- Connections shall be contained in a box. temp receptacle locations wiring stripped and hanging out of boxes.
314.25- Recessed junction box covers shall be completely installed as per instructions. Family room.
408.3(A)(2)- Barriers shall be installed ar service entrance line side terminals.
House OK to insulate, reinspect service.
ELE18-03484 Temporary Service9/13/20189/14/20189/14/2018 11:49:14 AMAPASS
Temp Power Phone #: ###-#### Inspection requested via web by Zane Robertson
t/s u/g n ok
ELE18-03483 Temporary Service9/13/20189/14/20189/14/2018 11:44:54 AMAPASS
Temp Power Phone #: ###-#### Inspection requested via web by Zane Robertson
t/s u/g n ok
ELE18-03526 Rough-In Permanent Service9/13/20189/14/20189/14/2018 11:34:24 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Informed that exposed und erground service conductors to temp poles must be covered by end of day.
Rough in ok cover p/s u/g n ok
ELE18-03520 Permanent Service9/13/20189/14/20189/14/2018 11:02:42 AMAPASS
Unit 103 service inspection Phone #: ###-#### Inspection requested via web by David Nelson
Approving due to tenants living at location. New panels in 806 and 103. Grounding electode conductor ran to underground metal water pipe only and shall be supplemented by additional rod as per 250.52. Will check on final.
p/s o/h rec ok
ELE18-02032 Electrical Rough-In9/14/20189/14/20189/14/2018 10:44:50 AMAPASS
Contact is Jim Noll ###-#### Phone #: ###-#### Inspection requested via web by Scott Campbell
West side picture columns and sign canopy, FMC not exposed to weather. Rough in ok covered
ELE17-03734 Final9/13/20189/14/20189/14/2018 10:24:56 AMAFAIL
Requesting partial final for TCO. Contact is Kory Peterson Phone #: ###-#### Inspection requested via web by Clint Tate
Contact informed me of Quality Electric are no longer open for business. A new contractor has taken over job. Areas are cluttered with equipment and areas are taped off so must reschedule when access available to all areas. Unable to locate general foreman or new electrical contractor.
ELE18-02941 Electrical Rough-In9/13/20189/14/20189/14/2018 10:19:55 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri
Excluding break area wall. Rest walls rough in ok cover.