ELE18-02233
| Final | 9/14/2018 | 9/14/2018 | 9/14/2018 3:23:39 PM | P | PASS |
|
|
Garage code 7573 Phone #: ###-#### Inspection requested via web by Bob Glenn Will check back in future to ensure hot tub has not been installed in areas in violation of NEC. Final ok
|
ELE18-02777
| Electrical Rough-In | 9/14/2018 | 9/14/2018 | 9/14/2018 2:57:23 PM | P | PASS |
|
|
Bar rough in inspection Phone #: ###-#### Inspection requested via web by Ryan Wake Bar wall rough in ok cover
|
ELE18-03533
| Electrical Rough-In | 9/14/2018 | 9/14/2018 | 9/14/2018 2:29:37 PM | P | FAIL |
|
|
Ron Phone #: ###-#### 517.13- Wiring methods in patient care space shall have a effective ground fault current path to all receptacle and switch locations with in patient care space. Confirm all receptacles and the switch in exam room E contain proper wiring method. Did not leave correction on site had verbal with Ron.
|
ELE18-03199
| Rough-In Permanent Service | 9/14/2018 | 9/14/2018 | 9/14/2018 1:53:28 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
|
ELE18-03507
| Rough-In Permanent Service | 9/13/2018 | 9/14/2018 | 9/14/2018 12:43:06 PM | A | FAIL |
|
|
call with any questions thank you Phone #: ###-#### Inspection requested via web by kim grundhauser 300.15- Connections shall be contained in a box. temp receptacle locations wiring stripped and hanging out of boxes. 314.25- Recessed junction box covers shall be completely installed as per instructions. Family room. 408.3(A)(2)- Barriers shall be installed ar service entrance line side terminals. House OK to insulate, reinspect service.
|
ELE18-03484
| Temporary Service | 9/13/2018 | 9/14/2018 | 9/14/2018 11:49:14 AM | A | PASS |
|
|
Temp Power Phone #: ###-#### Inspection requested via web by Zane Robertson t/s u/g n ok
|
ELE18-03483
| Temporary Service | 9/13/2018 | 9/14/2018 | 9/14/2018 11:44:54 AM | A | PASS |
|
|
Temp Power Phone #: ###-#### Inspection requested via web by Zane Robertson t/s u/g n ok
|
ELE18-03526
| Rough-In Permanent Service | 9/13/2018 | 9/14/2018 | 9/14/2018 11:34:24 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Informed that exposed und erground service conductors to temp poles must be covered by end of day. Rough in ok cover p/s u/g n ok
|
ELE18-03520
| Permanent Service | 9/13/2018 | 9/14/2018 | 9/14/2018 11:02:42 AM | A | PASS |
|
|
Unit 103 service inspection Phone #: ###-#### Inspection requested via web by David Nelson Approving due to tenants living at location. New panels in 806 and 103. Grounding electode conductor ran to underground metal water pipe only and shall be supplemented by additional rod as per 250.52. Will check on final. p/s o/h rec ok
|
ELE18-02032
| Electrical Rough-In | 9/14/2018 | 9/14/2018 | 9/14/2018 10:44:50 AM | A | PASS |
|
|
Contact is Jim Noll ###-#### Phone #: ###-#### Inspection requested via web by Scott Campbell West side picture columns and sign canopy, FMC not exposed to weather. Rough in ok covered
|
ELE17-03734
| Final | 9/13/2018 | 9/14/2018 | 9/14/2018 10:24:56 AM | A | FAIL |
|
|
Requesting partial final for TCO. Contact is Kory Peterson Phone #: ###-#### Inspection requested via web by Clint Tate Contact informed me of Quality Electric are no longer open for business. A new contractor has taken over job. Areas are cluttered with equipment and areas are taped off so must reschedule when access available to all areas. Unable to locate general foreman or new electrical contractor.
|
ELE18-02941
| Electrical Rough-In | 9/13/2018 | 9/14/2018 | 9/14/2018 10:19:55 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Excluding break area wall. Rest walls rough in ok cover.
|