Inspections for the day of: Thursday, September 15, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03370 Temporary Service9/15/20059/15/20059/15/2005 4:06:09 PMPFAIL
chris ###-#### called contr, left corr notice, fee due for re-inspection, 312.5 conductors entering enclosures shall be protected from abrasion, 250.53(G) rod electrode shall be 8' long and flush or below ground, 110.12(C) there shall be no broken parts,( 50a recpt and gec), 110.26(A)(1) work space shall be provided,BCC job id sticker shall be posted, address shall be posted
ELE05-03372 Temporary Service9/15/20059/15/20059/15/2005 3:47:22 PMPFAIL
chris ###-#### called contr, left corr notice, 250.24(C) grounded conductor shall be run to service disconnect and bonded, 200.7 grounded conductor shall be identified by color,312.5 conductors entering enclosures shall be protected from abrasion, 250.53(G) rod electrode shall be 8' long and flush or below ground, BCC job id sticker shall be posted, address shall be posted. re-inspection fee due.
ELE05-03371 Rough-In Permanent Service9/15/20059/15/20059/15/2005 3:05:26 PMPFAIL
doug ###-#### called contr, left corr notice, 300.4(D) 1 1/4" shall be maintained from edge of framing member, 110.12(C) nm cable jacketing shall not be cut, 210.52(H) hall over 10' shall have recpt, 210.52(A)(1)&(2) basement room shall have recpt in 2' wall and not over 12'
ELE05-02920 Final9/15/20059/15/20059/15/2005 2:28:21 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to final
ELE05-01800 Final9/14/20059/15/20059/15/2005 11:53:19 AMAPASS
dan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
ELE05-02158 Final9/13/20059/15/20059/15/2005 10:06:48 AMAPASS
warren; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final
ELE05-03363 Temporary Service9/14/20059/15/20059/15/2005 9:32:09 AMAPASS
###-#### - dan called contr about abrasion protection for gec. t/s u/g n ok
ELE05-03338 Rough-In Permanent Service9/13/20059/15/20059/15/2005 9:07:51 AMAPASS
darrell ###-#### ric ok, p/s u/g n ok
ELE05-03343 Electrical Rough-In9/14/20059/15/20059/15/2005 8:41:26 AMAPASS
john; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr about ko seal, strap mc, joint of mc not going anywhere. ric walls only ok