ELE05-03370
| Temporary Service | 9/15/2005 | 9/15/2005 | 9/15/2005 4:06:09 PM | P | FAIL |
|
|
chris ###-#### called contr, left corr notice, fee due for re-inspection, 312.5 conductors entering enclosures shall be protected from abrasion, 250.53(G) rod electrode shall be 8' long and flush or below ground, 110.12(C) there shall be no broken parts,( 50a recpt and gec), 110.26(A)(1) work space shall be provided,BCC job id sticker shall be posted, address shall be posted
|
ELE05-03372
| Temporary Service | 9/15/2005 | 9/15/2005 | 9/15/2005 3:47:22 PM | P | FAIL |
|
|
chris ###-#### called contr, left corr notice, 250.24(C) grounded conductor shall be run to service disconnect and bonded, 200.7 grounded conductor shall be identified by color,312.5 conductors entering enclosures shall be protected from abrasion, 250.53(G) rod electrode shall be 8' long and flush or below ground, BCC job id sticker shall be posted, address shall be posted. re-inspection fee due.
|
ELE05-03371
| Rough-In Permanent Service | 9/15/2005 | 9/15/2005 | 9/15/2005 3:05:26 PM | P | FAIL |
|
|
doug ###-#### called contr, left corr notice, 300.4(D) 1 1/4" shall be maintained from edge of framing member, 110.12(C) nm cable jacketing shall not be cut, 210.52(H) hall over 10' shall have recpt, 210.52(A)(1)&(2) basement room shall have recpt in 2' wall and not over 12'
|
ELE05-02920
| Final | 9/15/2005 | 9/15/2005 | 9/15/2005 2:28:21 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to final
|
ELE05-01800
| Final | 9/14/2005 | 9/15/2005 | 9/15/2005 11:53:19 AM | A | PASS |
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
|
ELE05-02158
| Final | 9/13/2005 | 9/15/2005 | 9/15/2005 10:06:48 AM | A | PASS |
|
|
warren; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final
|
ELE05-03363
| Temporary Service | 9/14/2005 | 9/15/2005 | 9/15/2005 9:32:09 AM | A | PASS |
|
|
###-#### - dan called contr about abrasion protection for gec. t/s u/g n ok
|
ELE05-03338
| Rough-In Permanent Service | 9/13/2005 | 9/15/2005 | 9/15/2005 9:07:51 AM | A | PASS |
|
|
darrell ###-#### ric ok, p/s u/g n ok
|
ELE05-03343
| Electrical Rough-In | 9/14/2005 | 9/15/2005 | 9/15/2005 8:41:26 AM | A | PASS |
|
|
john; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr about ko seal, strap mc, joint of mc not going anywhere. ric walls only ok
|