Inspections for the day of: Thursday, September 15, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00724 INSP-Final Inspection9/14/20059/15/20059/16/2005 3:08:58 PMAPART
Okay for final, however, the main control valves are shut at this time.
FIR05-00265 INSP-Sprinkler Rough-in9/14/20059/15/20059/16/2005 8:59:36 AMPPART
First floor lower office sprinkler rough-in is good for cover, also discussed uprights above drop ceiling at second level and garage door coverage in the warehouse area.
FIR05-00464 INSP-Sprinkler Rough-in/Hydro9/14/20059/15/20059/15/2005 5:05:44 PMAPART
UG hydrostatic test passed inspection, UG flushing performed after test was satisfactory.
BLD05-01757 FIRE-Final Inspection9/15/20059/15/20059/15/2005 4:34:28 PMPPASS
Items on correction notice have been completed, life safety finaled.
BLD05-01345 FIRE-Conference9/15/20059/15/20059/15/2005 4:08:17 PMPDONE
On site discussion with contractor regarding the proper location for duct smoke detectors.
FIR05-00190 INSP-Sprinkler Rough-in/Hydro9/15/20059/15/20059/15/2005 3:26:49 PMPCANC
No time for this inspection today, have rescheduled with contractor for friday am 9/16.
FIR05-00550 INSP-Alarm Testing9/15/20059/15/20059/15/2005 3:24:59 PMPPASS
Fire alarm passed inspection.
FIR05-00297 INSP-Sprinkler Rough-in/Hydro9/15/20059/15/20059/15/2005 2:22:10 PMPCANC
Inspection has been rescheduled for friday am 9/16/05.
FIR05-00297 INSP-Supply line flush9/15/20059/15/20059/15/2005 2:19:58 PMPPART
UG fire supply line flush is satisfactory.
FIR05-00335 INSP-Alarm Testing9/15/20059/15/20059/15/2005 1:18:41 PMPPASS
This permit has already been finaled on 7/1/05. Fire alarm permit finaled.
FIR05-00472 INSP-Final Inspection9/15/20059/15/20059/15/2005 11:55:57 AMPFAIL
Outside bells at both risers failed to function, duct smoke detectors tested okay, need record of signal verification at next inspection, still need sd cut sheet.
FIR05-00400 INSP-Sprinkler Rough-in/Hydro9/14/20059/15/20059/15/2005 11:52:27 AMAFAIL
Bushings are not allowed in this application at the fittings on the north side grid main see NFPA 13 6.4.6.1, provide seismic clearance for the 2" and 3" mains where they pass through the masonry wall, upright heads at the south attic are over 15' apart, inspectors test orfice is not correctly sized, provide approved plans at next inspection, provide relief valve for gridded system at riser.