Inspections for the day of: Friday, September 15, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03454 Electrical Rough-In9/15/20069/15/20069/15/2006 4:35:26 PMPFAIL
cal - call prior for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left corr notice, nec 210.52(A)(1) recpts shall be installed in mud room and top of stairs for 6'-12' spacing, 210.52(E) at least 1 recpt shall be at back of dwelling, 210.52(D) recpt shall be installed within 3' of each basin in bath, 210.11(C)(3) bath circuits shall be dedicated 20a branch circuits, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member, or covered with steel plates, 250.86 metal enclosure in hall for light shall be grounded, 210.12(B) bedrooms shall be afci protected, BCC all make-up shall be done, smoke detectors shall be installed in required areas, no violations shall be retained Note, later told contr that if no work done in room recpt would not have to be installed (bath)
ELE06-02921 Electrical Rough-In9/15/20069/15/20069/15/2006 4:15:37 PMPNR
mike Note: ceiling; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles met contr, left corr notice, fee due, nec 300.11 (A) support wires shall be secured at both ends, 330.30(A) cable shall be secured within12" of termination and not over 6', BCC work shall be ready for inspection and no remaining work to follow inspection
ELE06-02416 Electrical Rough-In9/15/20069/15/20069/15/2006 3:18:10 PMPPASS
ceiling inspection for Lees candies; Phone #: ###-#### Internet Inspection Request from: Jim Williams clg ok to cover, signed green card for part final and t/o, bldr not ready to sign regular t/o card, they will put in tunnel for customer access
ELE06-02555 Final9/15/20069/15/20069/15/2006 2:55:38 PMPPASS
joe; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, left survey, nec 210.63 125v recpt shall be within 25' of ac for servicing,404.9(A) sw plate shall seat against finished surface, ok to final
ELE06-02057 Final9/14/20069/15/20069/15/2006 12:18:39 PMAPASS
WE ARE READY FOR FINAL INSPECTION OF THE THEATER ROOM. THERE WILL BE AN EMPLOYEE OF THE STORE THERE ANY TIME AFTER 9:00 AM. BREN WOULD BE THE BEST CONTACT AT THE STORE AND IF YOU HAVE ANY OTHER QUESTIONS, PLEASE FEEL FREE TO CONTACT BRIAN KEITH AT THE OFFICE AT ###-####. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok to final
ELE06-02712 Final9/14/20069/15/20069/15/2006 11:56:15 AMAPASS
Daryl; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called contr about outside recpts, ok to final
ELE06-03444 Permanent Service9/14/20069/15/20069/15/2006 9:58:16 AMANR
robert ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, left corr notice, BCC no address, no job id sticker,no power or inspection shall be done without above
ELE06-02497 Final9/15/20069/15/20069/15/2006 9:43:11 AMAPASS
Scheduled by a contractor via Hello! on 9/15/2006 at 7:01:12 AM. Contact: ###-####. ok to final
ELE06-03281 Electrical Rough-In9/14/20069/15/20069/15/2006 9:34:13 AMPCANC
Please inspect partial B-wing underground in PM. Thanks; Phone #: ###-#### Internet Inspection Request from: Jim Friend Inspection cancelled from web by: Jim Friend
ELE06-02613 Electrical Rough-In9/14/20069/15/20069/15/2006 9:02:56 AMAPART
this is for a ceiling inspection, any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok to cover 6 office clgs only, 1st fl, left corr notice about rest of fixtures, nec 400.8 flexible cord and cables shall not be used as a substitue for the fixed wiring of a structure, talked to contr
ELE06-02309 Final9/14/20069/15/20069/15/2006 8:45:38 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok to final
ELE06-02750 Final9/15/20069/15/20069/15/2006 12:00:00 AMPCANC
joe; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles per joe cancelled