Inspections for the day of: Monday, September 15, 2008.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-02530 Electrical Rough-In9/15/20089/15/20089/15/2008 3:28:24 PMPPASS
underground Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ok to cover conduit under slab only
ELE08-02079 Final9/15/20089/15/20089/15/2008 3:04:59 PMPPASS
Bathrooms have been finaled but I need large open area finaled as well.We did some work in the ceiling area. Phone #: ###-#### Internet Inspection Request from: Lloyd Looney talked to contractor, ok to final, signed structural card, no esc this project
ESC07-01208 General Inspection9/15/20089/15/20089/15/2008 2:30:01 PMPPART
looked ok
ESC07-01278 General Inspection9/15/20089/15/20089/15/2008 2:29:00 PMPPART
looked ok
ESC07-00575 General Inspection9/15/20089/15/20089/15/2008 2:27:06 PMPPART
looked ok
ESC07-01326 General Inspection9/15/20089/15/20089/15/2008 2:24:41 PMAPART
looked ok
ESC07-01327 General Inspection9/15/20089/15/20089/15/2008 2:20:55 PMAPART
looked ok
ESC08-00384 General Inspection9/15/20089/15/20089/15/2008 1:46:07 PMAPART
looked ok
ELE08-00459 Final9/15/20089/15/20089/15/2008 1:24:07 PMPFAIL
Scheduled by a contractor via Hello! on 9/15/2008 at 8:18:41 AM. Contact: ###-####. called, left correction notice, NEC 330.30(A)&(B) approved securing devices shall be used and mc shall be secured within 12" of cable termination, 300.11(A) support wires shall provide secure support and be secured at both ends, BCC all work shall be completed, (front counter)
ELE07-03871 Final9/12/20089/15/20089/15/2008 12:28:19 PMPPASS
randall Phone #: ###-#### called owner, ok to final
ELE08-02409 Final9/12/20089/15/20089/15/2008 10:17:35 AMAFAIL
This is for the final inspection at this location. Mark Hood will be the contact. Thank you and have a great day! Phone #: ###-#### Internet Inspection Request from: Laura Longshaw called contractor, lef tcorrection notice, NEC 406.8(B) all outdoor receptacles shall be listed "WR", 406.11 all receptacles shall be tamper-resistant, no esc this project
ELE08-02527 Electrical Rough-In9/15/20089/15/20089/15/2008 9:45:07 AMACANC
underground Phone #: ###-#### Internet Inspection Request from: Therrin Robertson no bld, talked to contractor,wrong address see 7126 w victory
ELE08-02527 Temporary Service9/15/20089/15/20089/15/2008 9:42:33 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called, left correction notice,NEC 250.53(G) electrode shall be driven at angle not to exceed 45 degrees, 110.26(A) shall provide width and depth work space about equipment, 406.8(B) receptacles shall be listed "WR", BCC shall post job id sticker, NOTE wrong address- should be 7126, fee due, no esc for this listed project
ELE08-02514 Electrical Rough-In9/13/20089/15/20089/15/2008 9:16:44 AMAPASS
Scheduled by a contractor via Hello! on 9/13/2008 at 10:02:45 AM. Contact: ###-####. ric ok, no esc this project
ELE07-03623 Electrical Rough-In9/12/20089/15/20089/15/2008 8:50:51 AMAPASS
Doc Phone #: ###-#### soffits only ok to cover
ELE07-03622 Electrical Rough-In9/12/20089/15/20089/15/2008 8:33:56 AMAPASS
Doc Phone #: ###-#### soffits only ok to cover
ELE08-02525 Rough-In Permanent Service9/12/20089/15/20089/15/2008 8:20:43 AMAPASS
John Phone #: ###-#### ric ok both sides, p/s o/h n ok (2 meters)