ELE08-02530
| Electrical Rough-In | 9/15/2008 | 9/15/2008 | 9/15/2008 3:28:24 PM | P | PASS |
|
|
underground Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ok to cover conduit under slab only
|
ELE08-02079
| Final | 9/15/2008 | 9/15/2008 | 9/15/2008 3:04:59 PM | P | PASS |
|
|
Bathrooms have been finaled but I need large open area finaled as well.We did some work in the ceiling area. Phone #: ###-#### Internet Inspection Request from: Lloyd Looney talked to contractor, ok to final, signed structural card, no esc this project
|
ESC07-01208
| General Inspection | 9/15/2008 | 9/15/2008 | 9/15/2008 2:30:01 PM | P | PART |
|
|
looked ok
|
ESC07-01278
| General Inspection | 9/15/2008 | 9/15/2008 | 9/15/2008 2:29:00 PM | P | PART |
|
|
looked ok
|
ESC07-00575
| General Inspection | 9/15/2008 | 9/15/2008 | 9/15/2008 2:27:06 PM | P | PART |
|
|
looked ok
|
ESC07-01326
| General Inspection | 9/15/2008 | 9/15/2008 | 9/15/2008 2:24:41 PM | A | PART |
|
|
looked ok
|
ESC07-01327
| General Inspection | 9/15/2008 | 9/15/2008 | 9/15/2008 2:20:55 PM | A | PART |
|
|
looked ok
|
ESC08-00384
| General Inspection | 9/15/2008 | 9/15/2008 | 9/15/2008 1:46:07 PM | A | PART |
|
|
looked ok
|
ELE08-00459
| Final | 9/15/2008 | 9/15/2008 | 9/15/2008 1:24:07 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 9/15/2008 at 8:18:41 AM. Contact: ###-####. called, left correction notice, NEC 330.30(A)&(B) approved securing devices shall be used and mc shall be secured within 12" of cable termination, 300.11(A) support wires shall provide secure support and be secured at both ends, BCC all work shall be completed, (front counter)
|
ELE07-03871
| Final | 9/12/2008 | 9/15/2008 | 9/15/2008 12:28:19 PM | P | PASS |
|
|
randall Phone #: ###-#### called owner, ok to final
|
ELE08-02409
| Final | 9/12/2008 | 9/15/2008 | 9/15/2008 10:17:35 AM | A | FAIL |
|
|
This is for the final inspection at this location. Mark Hood will be the contact. Thank you and have a great day! Phone #: ###-#### Internet Inspection Request from: Laura Longshaw called contractor, lef tcorrection notice, NEC 406.8(B) all outdoor receptacles shall be listed "WR", 406.11 all receptacles shall be tamper-resistant, no esc this project
|
ELE08-02527
| Electrical Rough-In | 9/15/2008 | 9/15/2008 | 9/15/2008 9:45:07 AM | A | CANC |
|
|
underground Phone #: ###-#### Internet Inspection Request from: Therrin Robertson no bld, talked to contractor,wrong address see 7126 w victory
|
ELE08-02527
| Temporary Service | 9/15/2008 | 9/15/2008 | 9/15/2008 9:42:33 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called, left correction notice,NEC 250.53(G) electrode shall be driven at angle not to exceed 45 degrees, 110.26(A) shall provide width and depth work space about equipment, 406.8(B) receptacles shall be listed "WR", BCC shall post job id sticker, NOTE wrong address- should be 7126, fee due, no esc for this listed project
|
ELE08-02514
| Electrical Rough-In | 9/13/2008 | 9/15/2008 | 9/15/2008 9:16:44 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 9/13/2008 at 10:02:45 AM. Contact: ###-####. ric ok, no esc this project
|
ELE07-03623
| Electrical Rough-In | 9/12/2008 | 9/15/2008 | 9/15/2008 8:50:51 AM | A | PASS |
|
|
Doc Phone #: ###-#### soffits only ok to cover
|
ELE07-03622
| Electrical Rough-In | 9/12/2008 | 9/15/2008 | 9/15/2008 8:33:56 AM | A | PASS |
|
|
Doc Phone #: ###-#### soffits only ok to cover
|
ELE08-02525
| Rough-In Permanent Service | 9/12/2008 | 9/15/2008 | 9/15/2008 8:20:43 AM | A | PASS |
|
|
John Phone #: ###-#### ric ok both sides, p/s o/h n ok (2 meters)
|