Inspections for the day of: Monday, September 15, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00531 INSP-Sprinkler Rough-in9/12/20089/15/20089/15/2008 5:11:34 PMPFAIL
See the city approved plans for the locations of the deficiencies. They include flat faced bushings used in multiple locations which are not allowed per NFPA 13, sprinkler piping installed as 1" instead of the 1 1/4" as shown on the plans in the Sanctuary remote area, 11/4" piping installed where 1 1/2" piping is shown on the plans under the platform in the Sanctuary, the upright sprinkler heads located in the flat truss locations need to be centered in the truss space or aligned with the trusses as per NFPA 13, two upright sprinkler heads in the kitchen area are located too close to one another, the wron backflow preventor has been installed and 3" piping has been installed from the backflow preventor to the FDC tie in but the plans show 4", the riser detail shows 4" piping above the redi riser but 3" has been installed.
FIR08-00402 INSP-Sprinkler Rough-in/Hydro9/12/20089/15/20089/15/2008 3:56:30 PMAFAIL
The updated plans were not on site but Sam Rogers and I went ahead and conducted the single and the double head flow verifications. The single head test passed in both the single head remote area and when just a single head was flowed in the two head area. But when the two head test was performed not enought water was put out. Infact not enough water was available when measured right at the pump. No rough-in inspection of the piping has been performed yet.
FIR08-00429 INSP-Sprinkler Rough-in9/15/20089/15/20089/15/2008 3:51:04 PMPPASS
The piping in the mezzanine can be covered. An as-built has been provided showing the extension of the mezzanine and the additional sprinkler protection.
FIR08-00529 INSP-Final Inspection9/15/20089/15/20089/15/2008 3:42:44 PMPFAIL
The alarm signals are silencing and restoring themselves. The phone lines and battery signals are ok.
FIR08-00307 INSP-Final Inspection9/15/20089/15/20089/15/2008 2:01:01 PMPPASS
The hood suppression system operated correctly. Permit finaled.
BLD08-01396 FIRE-Final Inspection9/15/20089/15/20089/15/2008 1:05:10 PMPPASS
fire life safety passed
BLD08-01127 FIRE-Conference9/15/20089/15/20089/15/2008 12:03:24 PMADONE
The new office area in the existing building next to the breakroom is ok to occupy.See the city approved plans for the location signed and marked with todays date.
BLD08-01745 FIRE-Final Inspection9/15/20089/15/20089/15/2008 10:04:28 AMAPASS
Life safety passed