FIR08-00531
| INSP-Sprinkler Rough-in | 9/12/2008 | 9/15/2008 | 9/15/2008 5:11:34 PM | P | FAIL |
|
|
See the city approved plans for the locations of the deficiencies. They include flat faced bushings used in multiple locations which are not allowed per NFPA 13, sprinkler piping installed as 1" instead of the 1 1/4" as shown on the plans in the Sanctuary remote area, 11/4" piping installed where 1 1/2" piping is shown on the plans under the platform in the Sanctuary, the upright sprinkler heads located in the flat truss locations need to be centered in the truss space or aligned with the trusses as per NFPA 13, two upright sprinkler heads in the kitchen area are located too close to one another, the wron backflow preventor has been installed and 3" piping has been installed from the backflow preventor to the FDC tie in but the plans show 4", the riser detail shows 4" piping above the redi riser but 3" has been installed.
|
FIR08-00402
| INSP-Sprinkler Rough-in/Hydro | 9/12/2008 | 9/15/2008 | 9/15/2008 3:56:30 PM | A | FAIL |
|
|
The updated plans were not on site but Sam Rogers and I went ahead and conducted the single and the double head flow verifications. The single head test passed in both the single head remote area and when just a single head was flowed in the two head area. But when the two head test was performed not enought water was put out. Infact not enough water was available when measured right at the pump. No rough-in inspection of the piping has been performed yet.
|
FIR08-00429
| INSP-Sprinkler Rough-in | 9/15/2008 | 9/15/2008 | 9/15/2008 3:51:04 PM | P | PASS |
|
|
The piping in the mezzanine can be covered. An as-built has been provided showing the extension of the mezzanine and the additional sprinkler protection.
|
FIR08-00529
| INSP-Final Inspection | 9/15/2008 | 9/15/2008 | 9/15/2008 3:42:44 PM | P | FAIL |
|
|
The alarm signals are silencing and restoring themselves. The phone lines and battery signals are ok.
|
FIR08-00307
| INSP-Final Inspection | 9/15/2008 | 9/15/2008 | 9/15/2008 2:01:01 PM | P | PASS |
|
|
The hood suppression system operated correctly. Permit finaled.
|
BLD08-01396
| FIRE-Final Inspection | 9/15/2008 | 9/15/2008 | 9/15/2008 1:05:10 PM | P | PASS |
|
|
fire life safety passed
|
BLD08-01127
| FIRE-Conference | 9/15/2008 | 9/15/2008 | 9/15/2008 12:03:24 PM | A | DONE |
|
|
The new office area in the existing building next to the breakroom is ok to occupy.See the city approved plans for the location signed and marked with todays date.
|
BLD08-01745
| FIRE-Final Inspection | 9/15/2008 | 9/15/2008 | 9/15/2008 10:04:28 AM | A | PASS |
|
|
Life safety passed
|