FIR09-00369
| FIR-Aging Inspection | 9/15/2009 | 9/15/2009 | 9/15/2009 4:26:34 PM | | DONE |
|
|
|
FIR09-00435
| INSP-Sprinkler Rough-in | 9/14/2009 | 9/15/2009 | 9/15/2009 4:25:20 PM | P | PART |
|
|
Underground fire supply line and stub-in are approved for bury.
|
FIR09-00456
| INSP-Sprinkler Rough-in/Hydro | 9/15/2009 | 9/15/2009 | 9/15/2009 4:24:17 PM | P | PART |
|
|
Overhead work at rooms initialed with today's date on approved plans are okay for cover.
|
BLD09-01490
| FIRE-Final Inspection | 9/14/2009 | 9/15/2009 | 9/15/2009 4:22:57 PM | A | FAIL |
|
|
Need a current annual certification on the fire extinguisher, provide approved door hardware at the main entry/exit with signage, see items listed on general requirements page of issued documents.
|
FIR09-00420
| INSP-Final Inspection | 9/14/2009 | 9/15/2009 | 9/15/2009 4:20:48 PM | A | PASS |
|
|
Fire sprinkler work okayed for final.
|
FIR09-00365
| INSP-Final Inspection | 9/14/2009 | 9/15/2009 | 9/15/2009 4:20:01 PM | A | FAIL |
|
|
Need plan resubmittals due to significant changes in field installation and calc areas from what is shown on stamped drawings, also need to complete a hydrostatic test of the new piping and sprinklers.
|
FIR09-00521
| INSP-Final Inspection | 9/14/2009 | 9/15/2009 | 9/15/2009 4:16:46 PM | A | PASS |
|
|
Fire sprinkler permit finaled, inspections passed.
|
BLD08-01640
| FIRE-Final Inspection | 9/10/2009 | 9/15/2009 | 9/15/2009 4:13:52 PM | A | PART |
|
|
George Phone #: ###-####
|
BLD08-01143
| FIRE-Final Inspection | 9/14/2009 | 9/15/2009 | 9/15/2009 12:00:00 AM | A | PASS |
|
|
Final inspection satisfactory
|
FIR08-00448
| INSP-Final Inspection | 9/14/2009 | 9/15/2009 | 9/15/2009 12:00:00 AM | A | PASS |
|
|
Final inspection satisfactory
|
FIR08-00840
| INSP-Final Inspection | 9/14/2009 | 9/15/2009 | 9/15/2009 12:00:00 AM | A | PASS |
|
|
FInal Inspection satisfactory. Correction items completed.
|
BLD09-01356
| FIRE-Final Inspection | 9/14/2009 | 9/15/2009 | 9/15/2009 12:00:00 AM | A | PASS |
|
|
Door hardware corrections satisfactory. Sprinkler corrections will be completed under a seperate FIR permit.
|
BLD09-01554
| FIRE-Final Inspection | 9/14/2009 | 9/15/2009 | 9/15/2009 12:00:00 AM | P | PASS |
|
|
Inspection satisfactory.
|
BLD09-01558
| FIRE-Final Inspection | 9/14/2009 | 9/15/2009 | 9/15/2009 12:00:00 AM | P | PASS |
|
|
Inspection satisfactory.
|
FIR09-00485
| INSP-Final Inspection | 9/15/2009 | 9/15/2009 | 9/15/2009 12:00:00 AM | P | NR |
|
|
Not ready for final inspection. Ceiling tiles not installed at all sprinklers and multiple sprinklers missing escushions and/or concealer covers.
|