Inspections for the day of: Tuesday, September 15, 2009.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00369 FIR-Aging Inspection9/15/20099/15/20099/15/2009 4:26:34 PM DONE
FIR09-00435 INSP-Sprinkler Rough-in9/14/20099/15/20099/15/2009 4:25:20 PMPPART
Underground fire supply line and stub-in are approved for bury.
FIR09-00456 INSP-Sprinkler Rough-in/Hydro9/15/20099/15/20099/15/2009 4:24:17 PMPPART
Overhead work at rooms initialed with today's date on approved plans are okay for cover.
BLD09-01490 FIRE-Final Inspection9/14/20099/15/20099/15/2009 4:22:57 PMAFAIL
Need a current annual certification on the fire extinguisher, provide approved door hardware at the main entry/exit with signage, see items listed on general requirements page of issued documents.
FIR09-00420 INSP-Final Inspection9/14/20099/15/20099/15/2009 4:20:48 PMAPASS
Fire sprinkler work okayed for final.
FIR09-00365 INSP-Final Inspection9/14/20099/15/20099/15/2009 4:20:01 PMAFAIL
Need plan resubmittals due to significant changes in field installation and calc areas from what is shown on stamped drawings, also need to complete a hydrostatic test of the new piping and sprinklers.
FIR09-00521 INSP-Final Inspection9/14/20099/15/20099/15/2009 4:16:46 PMAPASS
Fire sprinkler permit finaled, inspections passed.
BLD08-01640 FIRE-Final Inspection9/10/20099/15/20099/15/2009 4:13:52 PMAPART
George Phone #: ###-####
BLD08-01143 FIRE-Final Inspection9/14/20099/15/20099/15/2009 12:00:00 AMAPASS
Final inspection satisfactory
FIR08-00448 INSP-Final Inspection9/14/20099/15/20099/15/2009 12:00:00 AMAPASS
Final inspection satisfactory
FIR08-00840 INSP-Final Inspection9/14/20099/15/20099/15/2009 12:00:00 AMAPASS
FInal Inspection satisfactory. Correction items completed.
BLD09-01356 FIRE-Final Inspection9/14/20099/15/20099/15/2009 12:00:00 AMAPASS
Door hardware corrections satisfactory. Sprinkler corrections will be completed under a seperate FIR permit.
BLD09-01554 FIRE-Final Inspection9/14/20099/15/20099/15/2009 12:00:00 AMPPASS
Inspection satisfactory.
BLD09-01558 FIRE-Final Inspection9/14/20099/15/20099/15/2009 12:00:00 AMPPASS
Inspection satisfactory.
FIR09-00485 INSP-Final Inspection9/15/20099/15/20099/15/2009 12:00:00 AMPNR
Not ready for final inspection. Ceiling tiles not installed at all sprinklers and multiple sprinklers missing escushions and/or concealer covers.