Inspections for the day of: Wednesday, September 15, 2010.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-02011 Temporary Service9/15/20109/15/20109/16/2010 1:57:15 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by steve cooper called, left correction notice, NEC 110.12(B) there shall be no broken parts, 406.8(B) receptacles shall be listed wr type, 250.53(G) upper end of electrode shall be flush with or below ground, 110.26(A) shall provide working space, BCC job id sticker shall be posted, shall clean interior debris from panel, fee due
ELE10-01982 Electrical Rough-In9/15/20109/15/20109/16/2010 10:59:50 AMPPASS
Phone #: ###-#### >> Inspection requested via web by joel smith ok to cover heat trace in driveway
ELE10-00847 Final9/14/20109/15/20109/16/2010 10:03:11 AMPPASS
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson ok final
ELE10-02016 Final9/14/20109/15/20109/16/2010 9:29:15 AMAPASS
We have completed the installation of the Exit Sign. Our Wireman is available at ###-#### (Todd). We left the Green Sticker with Wanita for the Exit Sign installation. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate ok final
ELE10-02018 Electrical Rough-In9/14/20109/15/20109/16/2010 9:11:37 AMAPASS
READY Phone #: ###-#### >> Inspection requested via web by Bob Glenn ri ok
ELE10-02038 Conference9/15/20109/15/20109/16/2010 9:07:20 AMPDONE
Gary Phone #: ###-#### talked about wiring addition, when to call for ri
ELE10-01286 Final9/14/20109/15/20109/16/2010 8:34:47 AMAPASS
George Phone #: ###-#### ok final
ELE10-02025 Rough-In Permanent Service9/14/20109/15/20109/16/2010 7:56:55 AMAPASS
Paul Phone #: ###-#### p/s o/h n ok
ELE10-01326 ELE-Aging Inspection9/15/20109/15/20109/16/2010 5:39:17 AM DONE
suc
ELE10-01307 ELE-Aging Inspection9/15/20109/15/20109/16/2010 5:38:33 AM DONE
suc
ELE10-00166 ELE-Aging Inspection9/15/20109/15/20109/16/2010 5:37:36 AM DONE
suc
ELE10-00118 ELE-Aging Inspection9/15/20109/15/20109/16/2010 5:36:48 AM DONE
suc
ELE09-00039 ELE-Aging Inspection9/15/20109/15/20109/16/2010 5:35:52 AM DONE
suc
ELE09-00036 ELE-Aging Inspection9/15/20109/15/20109/16/2010 5:33:14 AM DONE
see doc expire
ELE09-02271 ELE-Aging Inspection9/15/20109/15/20109/15/2010 8:14:54 AM CANC
Inspection cancelled from web by: joel smith