Inspections for the day of: Monday, September 15, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00070 INSP-Sprinkler Rough-in9/12/20149/15/20149/15/2014 4:49:40 PMPPART
UG fire supply line including the PIV and ductile riser okay for bury provided a plan modification is done to reflect changes in pipe route, added 45 and 90, and relocated riser room.
FIR14-00071 INSP-Sprinkler Rough-in9/12/20149/15/20149/15/2014 4:45:33 PMPPART
Revise thrust blocking at the 90 upstream of the ductile riser prior to cover.
FIR14-00556 INSP-Sprinkler Rough-in9/12/20149/15/20149/15/2014 4:43:27 PMPPART
UG fire supply line approved for cover.
FIR14-00554 INSP-Sprinkler Rough-in9/12/20149/15/20149/15/2014 4:42:41 PMPFAIL
UG work has been buried prior to inspection for cover.
FIR14-00432 INSP-Final Inspection9/12/20149/15/20149/15/2014 4:41:30 PMPNR
Communication fail at the panel.
BLD14-01237 FIRE-Final Inspection9/15/20149/15/20149/15/2014 4:40:28 PMPNR
Project related fire alarm and sprinkler permit finals pending.
FIR14-00442 INSP-Final Inspection9/12/20149/15/20149/15/2014 4:39:02 PMPNR
Incomplete due to project finishes.
BLD14-01761 FIRE-Final Inspection9/12/20149/15/20149/15/2014 2:52:49 PMPPASS
Verified C/N items on site.
BLD14-01951 FIRE-Final Inspection9/15/20149/15/20149/15/2014 11:55:05 AMPPASS
Fire life safety finaled.
BLD14-00650 FIRE-Final Inspection9/12/20149/15/20149/15/2014 11:54:14 AMAFAIL
Items noted include; reverse door hardware at the NW storage closet, extension cords are not to be used as a substitute for permanent power to appliances, repair gap at rated door to the second exit, threshold and overhead clearance at the exit doors from the assembly area are not compliant (missing ramp), post max occupancy sign per review note #9, sutie address does not match permit documents.
BLD14-01303 FIRE-Final Inspection9/13/20149/15/20149/15/2014 11:02:46 AMAPASS
Scope of work completed. Life safety inspection passed.
FIR14-00632 INSP-Sprinkler Rough-in9/12/20149/15/20149/15/2014 11:01:53 AMAPART
Overhead work at the elevator lobby sheetrock ceiling approved for cover.