Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM15-00158 PLM-Aging Inspection9/15/20159/15/20159/16/2015 1:59:05 PM PASS
PLM15-02365 Water and/or Sewer9/15/20159/15/20159/15/2015 4:21:00 PMPPEND
Phone #: ###-#### Inspection requested via web by Brent Lacy
>waiting on material specs
PLM15-03156 Water and/or Sewer9/15/20159/15/20159/15/2015 3:58:09 PMPPASS
PLM15-03140 Other9/14/20159/15/20159/15/2015 3:08:19 PMPFAIL
Pressure test Phone #: ###-#### Inspection requested via web by Raul Castanon
>pressure test failed @ 54psi
PLM15-02821 Plumbing Rough-in9/15/20159/15/20159/15/2015 2:29:53 PMPFAIL
STEVE RADY, CONTRACTOR, ###-####
Phone #: ###-#### Inspection requested via web by Chris Field
>1 Need permanent glue caps on demoed plumbing.
>2 Santee not approved for horizontal use @ wb
>3 must be 6" above flood level rim before turning horizontal @ mop sink upc 905.3
>4 leak at nipple on hot side of wh loop.
>5 retest and re inspect
PLM15-03009 Groundwork9/15/20159/15/20159/15/2015 1:52:56 PMPFAIL
Bill Phone #: ###-####
>1 DWV leak at 3x2 wye for shower, cut out and replace per 310.2 upc, unlawful to conceal hole with solvent cement.
>2 3" pipe at 22 does not enter hub square, redo
>3" drain is backgraded at santee for wc.
>4 2" shower drain needs 1/4" per ft grade
>5 make repairs and retest dwv
PLM15-01410 Final9/14/20159/15/20159/15/2015 1:28:20 PMPNR
MATT IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
PLM15-03157 Sprinkler (Final)9/15/20159/15/20159/15/2015 1:06:41 PMPPASS
Phone #: ###-#### Inspection requested via web by Darrell Roark
MIS15-00239 PLM-Final9/14/20159/15/20159/15/2015 11:33:40 AMAPART
>need to seperate rp feeding coke and coffee and add additional rp to coffee
>permit new rp that was installed for coke.
>building premise protection needs certified.
PLM14-03013 Final9/14/20159/15/20159/15/2015 10:39:49 AMAPASS
Home owner will be home and ready by 9 am. Thanks Troy Phone #: ###-#### Inspection requested via web by Troy Paulin
PLM15-02482 Final9/14/20159/15/20159/15/2015 10:21:55 AMAFAIL
Home owners will be home. Thanks you Troy Phone #: ###-#### Inspection requested via web by Troy Paulin
>need min 1" airgap at softener drain in washer box
PLM15-01723 Water and/or Sewer9/15/20159/15/20159/15/2015 9:56:39 AMAPART
Talk to Bill Vandergriff regarding sample ports. they are not needed Phone #: ###-#### Inspection requested via web by Raul Castanon
>incp venting ok
>incp inlet and outlet ok
>incp 24 test ok
PLM15-03142 Plumbing Rough-in9/14/20159/15/20159/15/2015 9:30:36 AMAPASS
Phone #: ###-#### Inspection requested via web by Tom Maxwell
PLM15-03156 Water and/or Sewer9/15/20159/15/20159/15/2015 9:14:19 AMAFAIL
Phone #: ###-#### Inspection requested via web by Brett Simmons
>unsuitable material around waterline, need 6" below water line with no rocks.
PLM15-03099 Water Heater Final9/9/20159/15/20159/14/2015 3:01:39 PMACANC
water heater final - Homeowner request am inspection. Please call Brian Neibaur when en route at ###-####. Thank you! Phone #: ###-#### >> Inspection requested via web by TERRY SIDWELL Inspection cancelled from web by: TERRY SIDWELL