Inspections for the day of: Monday, September 16, 2002.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-00828 FIRE-Final Inspection9/12/20029/16/20029/16/2002 12:00:00 AMAFAIL
###-#### sprinklers overspaced on southwest area of first floor; breakroom heads too close to each other on first floor; verify annual sprinkler inspection; escutcheons 9/16/2002 10:07:52 AM
FIR02-00352 INSP-Conference9/16/20029/16/20029/16/2002 12:00:00 AMAPART
met with Morey of Fire Sentry to verify locations of smoke detectors; not overspaced where new back boxes are installed
FIR02-00365 INSP-Conference9/16/20029/16/20029/16/2002 12:00:00 AMAPART
met with Scott Apple and requested Bill ALexander to check this work out; all agree that webbing must be cleaned better or remove webbing
BLD02-01874 FIRE-Final Inspection9/16/20029/16/20029/16/2002 12:00:00 AMPPASS
###-####
BLD02-01601 FIRE-Sprinkler Rough-in9/16/20029/16/20029/16/2002 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 09/16/2002 at 08:43:55. Contact: ###-####. okay to cover; plans not required per plan review notes 9/16/2002 3:18:32 PM
BLD02-01253 FIRE-Final Inspection9/10/20029/16/20029/16/2002 12:00:00 AMPCANC
dan- ###-#### rescehduled for 9/17 per Dan 9/16/2002 1:16:34 PM
BLD02-01300 FIRE-Final Inspection9/10/20029/16/20029/16/2002 12:00:00 AMPCANC
dan; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie rescheduled for 9/17 per Dan 9/16/2002 1:16:17 PM
FIR02-00307 INSP-Sprinkler Rough-in9/12/20029/16/20029/16/2002 12:00:00 AMPFAIL
fire pump test; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung pump test was okay; see approved plans for areas failed - need additional EQ in storage area; heads overspaced by wall in SE storage area; verify heads in carasuels for type commodity; fire caulk penetration in occ separation wall; add clamp on 4 way in hallway; addadditional spare heads in head box; verify all end of lines have hanger within 12 inches as system is over 100 psi now; lower stock to below 22 feet (recommend markers on racks to identify 22 ft; add calc stickers, etc; inspector to witness test of all pump controller/tampers, etc 9/16/2002 2:56:56 PM