BLD02-00828
| FIRE-Final Inspection | 9/12/2002 | 9/16/2002 | 9/16/2002 12:00:00 AM | A | FAIL |
|
|
###-#### sprinklers overspaced on southwest area of first floor; breakroom heads too close to each other on first floor; verify annual sprinkler inspection; escutcheons 9/16/2002 10:07:52 AM
|
FIR02-00352
| INSP-Conference | 9/16/2002 | 9/16/2002 | 9/16/2002 12:00:00 AM | A | PART |
|
|
met with Morey of Fire Sentry to verify locations of smoke detectors; not overspaced where new back boxes are installed
|
FIR02-00365
| INSP-Conference | 9/16/2002 | 9/16/2002 | 9/16/2002 12:00:00 AM | A | PART |
|
|
met with Scott Apple and requested Bill ALexander to check this work out; all agree that webbing must be cleaned better or remove webbing
|
BLD02-01874
| FIRE-Final Inspection | 9/16/2002 | 9/16/2002 | 9/16/2002 12:00:00 AM | P | PASS |
|
|
###-####
|
BLD02-01601
| FIRE-Sprinkler Rough-in | 9/16/2002 | 9/16/2002 | 9/16/2002 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 09/16/2002 at 08:43:55. Contact: ###-####. okay to cover; plans not required per plan review notes 9/16/2002 3:18:32 PM
|
BLD02-01253
| FIRE-Final Inspection | 9/10/2002 | 9/16/2002 | 9/16/2002 12:00:00 AM | P | CANC |
|
|
dan- ###-#### rescehduled for 9/17 per Dan 9/16/2002 1:16:34 PM
|
BLD02-01300
| FIRE-Final Inspection | 9/10/2002 | 9/16/2002 | 9/16/2002 12:00:00 AM | P | CANC |
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie rescheduled for 9/17 per Dan 9/16/2002 1:16:17 PM
|
FIR02-00307
| INSP-Sprinkler Rough-in | 9/12/2002 | 9/16/2002 | 9/16/2002 12:00:00 AM | P | FAIL |
|
|
fire pump test; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung pump test was okay; see approved plans for areas failed - need additional EQ in storage area; heads overspaced by wall in SE storage area; verify heads in carasuels for type commodity; fire caulk penetration in occ separation wall; add clamp on 4 way in hallway; addadditional spare heads in head box; verify all end of lines have hanger within 12 inches as system is over 100 psi now; lower stock to below 22 feet (recommend markers on racks to identify 22 ft; add calc stickers, etc; inspector to witness test of all pump controller/tampers, etc 9/16/2002 2:56:56 PM
|