BLD05-01707
| FIRE-Final Inspection | 9/15/2005 | 9/16/2005 | 9/16/2005 4:01:19 PM | P | CANC |
|
|
|
BLD05-01927
| FIRE-Final Inspection | 9/15/2005 | 9/16/2005 | 9/16/2005 4:00:38 PM | P | CANC |
|
|
|
FIR05-00515
| INSP-Final Inspection | 9/15/2005 | 9/16/2005 | 9/16/2005 3:59:30 PM | P | CANC |
|
|
|
BLD05-01926
| FIRE-Final Inspection | 9/15/2005 | 9/16/2005 | 9/16/2005 3:58:51 PM | P | CANC |
|
|
|
FIR05-00514
| INSP-Final Inspection | 9/15/2005 | 9/16/2005 | 9/16/2005 3:58:23 PM | P | CANC |
|
|
|
MIS05-00124
| FIR-Final | 9/15/2005 | 9/16/2005 | 9/16/2005 3:33:54 PM | P | FAIL |
|
|
Provide building address numbers, provide approved door hardware at exit doors as discussed.
|
BLD05-02029
| FIRE-Final Inspection | 9/15/2005 | 9/16/2005 | 9/16/2005 3:01:23 PM | A | CANC |
|
|
Cancel inspection per Scott, the HVAC duct smoke detectors are not completed.
|
FIR05-00522
| INSP-Final Inspection | 9/15/2005 | 9/16/2005 | 9/16/2005 2:59:28 PM | A | PART |
|
|
Overhead sprinkler rough-in is good for cover, except one retaining strap at confrence room 356 is not attatched to the beam.
|
BLD05-01981
| FIRE-Final Inspection | 9/15/2005 | 9/16/2005 | 9/16/2005 12:54:16 PM | A | PASS |
|
|
Fire life safety passed inspection.
|
FIR05-00297
| INSP-Sprinkler Rough-in | 9/15/2005 | 9/16/2005 | 9/16/2005 12:26:29 PM | A | FAIL |
|
|
Coverage is lacking under stairs at first floor, 3/4 upright heads in four locations as marked on approved plans exceed minimum spacing allowance, some sprigs at first floor corridor are not vertical, elevator pit needs the sw heads and cages installed, verify heads in stairway are 155 degree, pipe drain from ball drip at west FDC to an approved location, the riser and ceilings in exit corridors are not complete yet, this inspection was for BODO 4 two story building.
|
FIR05-00190
| INSP-Sprinkler Rough-in | 9/15/2005 | 9/16/2005 | 9/16/2005 10:27:37 AM | A | PART |
|
|
Overhead rough-in for system 10 west side sheet FP1 is acceptable to cover.
|
BLD04-02867
| FIRE-Final Inspection | 9/15/2005 | 9/16/2005 | 9/16/2005 9:34:40 AM | A | PASS |
|
|
Life safety passed inspection.
|
FIR05-00089
| INSP-Sprinkler Rough-in | 9/16/2005 | 9/16/2005 | 9/16/2005 12:00:00 AM | A | FAIL |
|
|
See approved plans for annotations of defficient areas, this inspection was called in under the wrong permit number fir05-00297 for the adjacent 4 story Foster building.
|
FIR05-00549
| INSP-Final Inspection | 9/16/2005 | 9/16/2005 | 9/16/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR05-00550
| INSP-Final Inspection | 9/16/2005 | 9/16/2005 | 9/16/2005 12:00:00 AM | P | PASS |
|
|
Fire alarm finaled.
|
FIR05-00379
| INSP-Final Inspection | 9/16/2005 | 9/16/2005 | 9/16/2005 12:00:00 AM | P | PASS |
|
|
Fire alarm finaled.
|