Inspections for the day of: Friday, September 16, 2005.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-01707 FIRE-Final Inspection9/15/20059/16/20059/16/2005 4:01:19 PMPCANC
BLD05-01927 FIRE-Final Inspection9/15/20059/16/20059/16/2005 4:00:38 PMPCANC
FIR05-00515 INSP-Final Inspection9/15/20059/16/20059/16/2005 3:59:30 PMPCANC
BLD05-01926 FIRE-Final Inspection9/15/20059/16/20059/16/2005 3:58:51 PMPCANC
FIR05-00514 INSP-Final Inspection9/15/20059/16/20059/16/2005 3:58:23 PMPCANC
MIS05-00124 FIR-Final9/15/20059/16/20059/16/2005 3:33:54 PMPFAIL
Provide building address numbers, provide approved door hardware at exit doors as discussed.
BLD05-02029 FIRE-Final Inspection9/15/20059/16/20059/16/2005 3:01:23 PMACANC
Cancel inspection per Scott, the HVAC duct smoke detectors are not completed.
FIR05-00522 INSP-Final Inspection9/15/20059/16/20059/16/2005 2:59:28 PMAPART
Overhead sprinkler rough-in is good for cover, except one retaining strap at confrence room 356 is not attatched to the beam.
BLD05-01981 FIRE-Final Inspection9/15/20059/16/20059/16/2005 12:54:16 PMAPASS
Fire life safety passed inspection.
FIR05-00297 INSP-Sprinkler Rough-in9/15/20059/16/20059/16/2005 12:26:29 PMAFAIL
Coverage is lacking under stairs at first floor, 3/4 upright heads in four locations as marked on approved plans exceed minimum spacing allowance, some sprigs at first floor corridor are not vertical, elevator pit needs the sw heads and cages installed, verify heads in stairway are 155 degree, pipe drain from ball drip at west FDC to an approved location, the riser and ceilings in exit corridors are not complete yet, this inspection was for BODO 4 two story building.
FIR05-00190 INSP-Sprinkler Rough-in9/15/20059/16/20059/16/2005 10:27:37 AMAPART
Overhead rough-in for system 10 west side sheet FP1 is acceptable to cover.
BLD04-02867 FIRE-Final Inspection9/15/20059/16/20059/16/2005 9:34:40 AMAPASS
Life safety passed inspection.
FIR05-00089 INSP-Sprinkler Rough-in9/16/20059/16/20059/16/2005 12:00:00 AMAFAIL
See approved plans for annotations of defficient areas, this inspection was called in under the wrong permit number fir05-00297 for the adjacent 4 story Foster building.
FIR05-00549 INSP-Final Inspection9/16/20059/16/20059/16/2005 12:00:00 AMPPASS
Fire sprinkler permit finaled.
FIR05-00550 INSP-Final Inspection9/16/20059/16/20059/16/2005 12:00:00 AMPPASS
Fire alarm finaled.
FIR05-00379 INSP-Final Inspection9/16/20059/16/20059/16/2005 12:00:00 AMPPASS
Fire alarm finaled.