FIR05-00518
| INSP-Final Inspection | 9/16/2008 | 9/16/2008 | 9/19/2008 3:58:45 PM | P | PASS |
|
|
Permit finaled
|
FIR08-00402
| INSP-Sprinkler Rough-in | 9/16/2008 | 9/16/2008 | 9/17/2008 2:34:13 PM | P | PART |
|
|
The bucket test passed. The two head area flowed 31 gallons and the single head area flowed 22 gallons. I gave the ok to cover the piping with the condition that as-built plans and hydraulic calculations are re-submitted to the city. This is due to the interconnecting piping to and between the four manifolds, as installed, does not match the city approved plans.
|
FIR08-00322
| INSP-Final Inspection | 9/16/2008 | 9/16/2008 | 9/17/2008 11:14:45 AM | P | PASS |
|
|
permit finaled
|
FIR08-00638
| INSP-Conference | 9/16/2008 | 9/16/2008 | 9/16/2008 3:27:01 PM | P | DONE |
|
|
Mark Senteno and I agreed that the manual activation for the hood suppression can be placed on the left hand side of the east exterior exit door.
|
FIR08-00627
| INSP-Sprinkler Rough-in/Hydro | 9/16/2008 | 9/16/2008 | 9/16/2008 3:25:40 PM | P | PASS |
|
|
Todays inspection was for just the 12'-0" of 6" stub-out. This underground piping is ok to bury.
|
BLD08-01786
| FIRE-Final Inspection | 9/16/2008 | 9/16/2008 | 9/16/2008 2:46:28 PM | P | FAIL |
|
|
The project was not ready for a final inspection yet but we verified that the smoke evacuation system operated correctly.
|
BLD08-00622
| FIRE-Conference | 9/16/2008 | 9/16/2008 | 9/16/2008 2:45:15 PM | P | CANC |
|
|
The conference was not required on site and was taken care of over the phone.
|
FIR05-00596
| INSP-Final Inspection | 9/16/2008 | 9/16/2008 | 9/16/2008 11:27:11 AM | A | PASS |
|
|
Permit finaled
|
FIR05-00836
| INSP-Final Inspection | 9/16/2008 | 9/16/2008 | 9/16/2008 11:00:42 AM | A | PASS |
|
|
Permit finaled
|