PLM09-01390
| Sprinkler (Final) | 9/16/2009 | 9/16/2009 | 9/16/2009 4:47:16 PM | P | FAIL |
|
|
Hans Phone #: ###-#### need to use approved material for connection to potable water...............ds
|
PLM09-01566
| Plumbing Rough-in | 9/16/2009 | 9/16/2009 | 9/16/2009 4:33:08 PM | P | PASS |
|
|
Please call Ryan with Wallace Const. and he will let you in ###-####. Phone #: ###-#### Internet Inspection Request from: Jennifer Alcala
|
PLM08-02046
| Other | 9/16/2009 | 9/16/2009 | 9/16/2009 4:10:35 PM | P | PASS |
|
|
Xavier-if possible before 3 please Phone #: ###-####
|
PLM09-01562
| Water and/or Sewer | 9/16/2009 | 9/16/2009 | 9/16/2009 3:56:19 PM | P | PASS |
|
|
randy - please call 1/2 hr prior Phone #: ###-####
|
PLM09-01562
| Final | 9/16/2009 | 9/16/2009 | 9/16/2009 3:56:10 PM | P | PASS |
|
|
randy - please call 1/2 hr prior Phone #: ###-####
|
PLM09-01548
| Water and/or Sewer | 9/16/2009 | 9/16/2009 | 9/16/2009 3:32:47 PM | P | PART |
|
|
Jim Phone #: ###-#### water ok........sewer has a leak in a coupling up near the house..........ds
|
PLM09-00241
| Final | 9/16/2009 | 9/16/2009 | 9/16/2009 2:53:57 PM | P | PASS |
|
|
Don Phone #: ###-####
|
PLM09-00043
| Final | 9/16/2009 | 9/16/2009 | 9/16/2009 2:52:46 PM | P | PASS |
|
|
Don Phone #: ###-####
|
PLM09-00244
| Final | 9/16/2009 | 9/16/2009 | 9/16/2009 2:51:36 PM | P | PASS |
|
|
Don Phone #: ###-####
|
PLM09-00243
| Final | 9/16/2009 | 9/16/2009 | 9/16/2009 2:51:23 PM | P | PASS |
|
|
Don Phone #: ###-####
|
PLM09-01301
| Groundwork | 9/15/2009 | 9/16/2009 | 9/16/2009 2:03:04 PM | P | CANC |
|
|
ROUGH WASTE & VENT - CALL MIKE TO SCHEDULE ###-#### Phone #: ###-#### Internet Inspection Request from: Allison Briggs
|
PLM09-01301
| Plumbing Rough-in | 9/16/2009 | 9/16/2009 | 9/16/2009 2:02:56 PM | P | PASS |
|
|
ROUGH WASTE & VENT - CALL MIKE TO SCHEDULE ###-#### Phone #: ###-#### Internet Inspection Request from: Allison Briggs
|
PLM08-02349
| Final | 9/15/2009 | 9/16/2009 | 9/16/2009 11:45:02 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Burton Friesz
|
PLM09-01553
| Final | 9/15/2009 | 9/16/2009 | 9/16/2009 11:29:49 AM | A | CANC |
|
|
|
GCP09-00009
| GCP- Rough-in | 9/16/2009 | 9/16/2009 | 9/16/2009 10:53:29 AM | P | FAIL |
|
|
Hot water to upstairs lav must be tempered. UPC 2003 414.1 Cannot install pex piping within first 18 inches of water heater connection. UPC 2003 604.11.2 .........ds
|
PLM09-01534
| Plumbing Rough-in | 9/15/2009 | 9/16/2009 | 9/16/2009 9:54:07 AM | A | PASS |
|
|
will Phone #: ###-####
|
PLM09-01060
| Final | 9/14/2009 | 9/16/2009 | 9/16/2009 9:31:55 AM | A | PASS |
|
|
final with home owner thanks Phone #: ###-#### Internet Inspection Request from: fritz ramisch
|